343998647
|
0213100
|
2019-05-07
|
16 SHERIDAN AVE, ALBANY, NY, 12203
|
|
Inspection Type |
Complaint
|
Scope |
Partial
|
Safety/Health |
Safety
|
Close Conference |
2019-05-07
|
Emphasis |
L: LOCALTARG, P: LOCALTARG
|
Case Closed |
2019-09-24
|
Related Activity
Type |
Complaint |
Activity Nr |
1451534 |
Safety |
Yes |
|
Violation Items
Citation ID |
01001 |
Citaton Type |
Repeat |
Standard Cited |
19260405 B01 |
Issuance Date |
2019-06-28 |
Abatement Due Date |
2019-07-08 |
Current Penalty |
0.0 |
Initial Penalty |
6062.0 |
Final Order |
2019-08-05 |
Nr Instances |
1 |
Nr Exposed |
20 |
Related Event Code (REC) |
Complaint |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1926.405(b)(1): Unused openings in cabinets, boxes and fittings were not effectively closed. a) On May 7, 2019, and at times prior two openings on the top of panel box "power 5," on the 3rd floor, were not effectively closed, which exposed employees to energized parts inside. The JJMS/ DBA Prediletto Electric was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1926.405(b)(1), which was contained in OSHA inspection number 1071064, citation number 1, item number 4/a and was affirmed as a final order on September 16, 2015, with respect to a workplace located at 733 Broadway, Albany, NY. |
|
Citation ID |
02001 |
Citaton Type |
Other |
Standard Cited |
19260403 H |
Issuance Date |
2019-06-28 |
Abatement Due Date |
2019-07-09 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2019-08-05 |
Nr Instances |
2 |
Nr Exposed |
20 |
Related Event Code (REC) |
Complaint |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1926.403(h): Each service, feeder, and branch circuit was not legibly marked at its disconnecting means or overcurrent device to indicate its purpose, nor located and arranged so that the purpose is evident. a) on May 7, 2019. and at times prior, 3rd floor, circuit breakers in temporary power panel boxes labeled "power 5" were not marked to indicate purpose. b) on May 7, 2019. and at times prior, 4th floor, circuit breakers in temporary power panel box labeled "power 7" were not marked to indicate purpose. |
|
|
340710649
|
0213100
|
2015-06-16
|
733 BROADWAY, ALBANY, NY, 12207
|
|
Inspection Type |
Complaint
|
Scope |
Partial
|
Safety/Health |
Safety
|
Close Conference |
2015-06-16
|
Case Closed |
2016-02-04
|
Related Activity
Type |
Complaint |
Activity Nr |
992160 |
Safety |
Yes |
|
Type |
Inspection |
Activity Nr |
1070921 |
Safety |
Yes |
|
Violation Items
Citation ID |
01001A |
Citaton Type |
Serious |
Standard Cited |
19260403 B02 |
Issuance Date |
2015-08-26 |
Abatement Due Date |
2015-09-01 |
Current Penalty |
1000.0 |
Initial Penalty |
2800.0 |
Final Order |
2015-09-16 |
Nr Instances |
3 |
Nr Exposed |
4 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification: a) 733 Broadway, Albany NY. - On or about June 16th, 2015 - Three steel double gang square boxes with 1/2-Inch and 3/4-Inch Knockouts were not mounted to the walls in their areas. The conduit boxes were not designed for the application. Employees were exposed to electrical shock hazards. |
|
Citation ID |
01001B |
Citaton Type |
Serious |
Standard Cited |
19260405 A02 II F |
Issuance Date |
2015-08-26 |
Abatement Due Date |
2015-09-01 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2015-09-16 |
Nr Instances |
1 |
Nr Exposed |
4 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1926.405(a)(2)(ii)(F): Temporary lights were suspended by their electric cords when such lights and cords were not designed for suspension: a) 733 Broadway, Albany NY. - On or about June 16th, 2015 - Temporary string lighting was suspended by its cord throughout the work site. The stringers were not designed for the application. Employees were exposed to fire and electrical shock hazards. |
|
Citation ID |
01004A |
Citaton Type |
Serious |
Standard Cited |
19260405 B01 |
Issuance Date |
2015-08-26 |
Abatement Due Date |
2015-09-01 |
Current Penalty |
1000.0 |
Initial Penalty |
2000.0 |
Final Order |
2015-09-16 |
Nr Instances |
1 |
Nr Exposed |
4 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1926.405(b)(1): Unused openings in cabinets, boxes, and fittings were not effectively closed: a) 733 Broadway, Albany NY. - On or about June 16th, 2015 - A panel box providing temporary power for the job site had various unused openings that were not closed. Employees were exposed to electrical shock hazards due to the openings. |
|
Citation ID |
01004B |
Citaton Type |
Serious |
Standard Cited |
19260405 B02 |
Issuance Date |
2015-08-26 |
Abatement Due Date |
2015-09-01 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2015-09-16 |
Nr Instances |
2 |
Nr Exposed |
4 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1926.405(b)(2): All pull boxes, junction boxes, and fittings were not provided with covers: a) 733 Broadway, Albany NY. - On or about June 16th, 2015 - A panel box was installed and providing power to various areas of the work site. The panel box was not provided with a cover. Employees were exposed to electrical shock hazards. b) 733 Broadway, Albany NY. - On or about June 16th, 2015 - Three double gang outlets that were mounted next to a panel box did not have covers. Employees were exposed to electrical shock hazards. |
|
Citation ID |
01004C |
Citaton Type |
Serious |
Standard Cited |
19260405 J01 I |
Issuance Date |
2015-08-26 |
Abatement Due Date |
2015-09-01 |
Current Penalty |
0.0 |
Initial Penalty |
1200.0 |
Final Order |
2015-09-16 |
Nr Instances |
1 |
Nr Exposed |
4 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1926.405(j)(1)(i): Fixtures, lampholders, lamps, rosettes, or receptacles had live parts normally exposed to employee contact: a) 733 Broadway, Albany NY. - On or about June 16th, 2015 - A temporary light receptacle was missing its cover and bulb. The 120 volt fixture was exposed to employee contact while lying on the floor. Employees were exposed to electrical shock hazards. |
|
|