Inspection Type |
Planned
|
Scope |
Partial
|
Safety/Health |
Safety
|
Close Conference |
2013-08-13
|
Emphasis |
P: AMPUTATE, N: AMPUTATE
|
Case Closed |
2014-02-10
|
Violation Items
Citation ID |
01001 |
Citaton Type |
Serious |
Standard Cited |
19100024 H |
Issuance Date |
2013-08-21 |
Abatement Due Date |
2013-10-21 |
Current Penalty |
765.0 |
Initial Penalty |
1020.0 |
Final Order |
2013-09-13 |
Nr Instances |
1 |
Nr Exposed |
2 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.24(h): Standard railings were not provided on the open sides of all exposed stairways and stair platforms: a) On or about 08/12/13, in the Pre-Press Area, the stairway/stair landing leading to the Pre-Press Room on the second floor did not have a standard railing exposing employees to falls of 52 inches. ABATEMENT CERTIFICATION REQUIRED |
|
Citation ID |
01002 |
Citaton Type |
Serious |
Standard Cited |
19100147 C04 I |
Issuance Date |
2013-08-21 |
Abatement Due Date |
2013-10-21 |
Current Penalty |
1020.0 |
Initial Penalty |
1360.0 |
Final Order |
2013-09-13 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section: a) On or about 08/12/13, in the Pre-Press Areas, a Lockout/Tagout procedure was not utilized while cleaning parts inside of a plate processor machine: Pro Raptor 85 S. ABATEMENT CERTIFICATION REQUIRED |
|
Citation ID |
01003 |
Citaton Type |
Serious |
Standard Cited |
19100151 C |
Issuance Date |
2013-08-21 |
Abatement Due Date |
2013-10-21 |
Current Penalty |
1020.0 |
Initial Penalty |
1360.0 |
Final Order |
2013-09-13 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use: a) On or about 08/12/13, in the Pro Raptor 85 S plate processor room, there was not an emergency eye wash unit immediately adjacent to the area where employees were handling corrosive chemicals such as, but not limited to: L5000b Ultra Developer. ABATEMENT CERTIFICATION REQUIRED |
|
Citation ID |
02001 |
Citaton Type |
Other |
Standard Cited |
19100037 B02 |
Issuance Date |
2013-08-21 |
Abatement Due Date |
2013-10-21 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2013-09-13 |
Nr Instances |
1 |
Nr Exposed |
3 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit": a) On or about 08/12/13, in the Bindery area, an exit door did not have an "Exit" sign posted. ABATEMENT CERTIFICATION REQUIRED |
|
Citation ID |
02002 |
Citaton Type |
Other |
Standard Cited |
19100303 G01 |
Issuance Date |
2013-08-21 |
Abatement Due Date |
2013-10-21 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2013-09-13 |
Nr Instances |
1 |
Nr Exposed |
2 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: a) On or about 08/12/13, in the press area, an electrical panel access was blocked by a broom, a dustpan and wooden mini-tables/pallets. ABATEMENT CERTIFICATION REQUIRED |
|
|