Citation ID |
01001 |
Citaton Type |
Serious |
Standard Cited |
19100022 A01 |
Issuance Date |
2012-08-03 |
Abatement Due Date |
2012-08-10 |
Current Penalty |
1620.0 |
Initial Penalty |
2700.0 |
Contest Date |
2012-08-24 |
Final Order |
2013-03-13 |
Nr Instances |
1 |
Nr Exposed |
4 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.22(a)(1): All places of employment, passageways, storerooms or service rooms were not kept clean and orderly or in a sanitary condition: a) On or about 5/10/2012, Gluten Free Area: The floor was coated with oil near the Hot Press. Abatement certification is required for this item. |
|
Citation ID |
01002A |
Citaton Type |
Serious |
Standard Cited |
19100037 A03 |
Issuance Date |
2012-08-03 |
Abatement Due Date |
2012-08-10 |
Current Penalty |
0.0 |
Initial Penalty |
3600.0 |
Contest Date |
2012-08-24 |
Final Order |
2013-03-13 |
Nr Instances |
1 |
Nr Exposed |
4 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed: a) On or about 5/10/2012, Main Holding Freezer: The West exit door was blocked by a pallet of product and a trash can. Abatement certification is required for this item. |
|
Citation ID |
01002B |
Citaton Type |
Serious |
Standard Cited |
19100037 A04 |
Issuance Date |
2012-08-03 |
Abatement Due Date |
2012-08-10 |
Current Penalty |
1620.0 |
Initial Penalty |
0.0 |
Contest Date |
2012-08-24 |
Final Order |
2013-03-13 |
Nr Instances |
2 |
Nr Exposed |
4 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.37(a)(4): Safeguard(s) designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting), were not in proper working order at all times: a) On or about 5/10/2012, South Hallway: Emergency lighting was not functional. b) On or about 5/10/2012, Back Office Hallway: Emergency lighting was not functional. Abatement certification is required for this item. |
|
Citation ID |
01002C |
Citaton Type |
Serious |
Standard Cited |
19100037 B02 |
Issuance Date |
2012-08-03 |
Abatement Due Date |
2012-08-10 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Contest Date |
2012-08-24 |
Final Order |
2013-03-13 |
Nr Instances |
2 |
Nr Exposed |
4 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit": a) On or about 5/10/2012, Main Holding Freezer: The West exit door was not marked with an exit sign. b) On or about 5/10/2012, Line #4 Area: Two exits from the line #4 area were not provided with exit signs. Abatement certification is required for this item. |
|
Citation ID |
01003 |
Citaton Type |
Serious |
Standard Cited |
19100151 C |
Issuance Date |
2012-08-03 |
Abatement Due Date |
2012-08-10 |
Current Penalty |
2160.0 |
Initial Penalty |
3600.0 |
Contest Date |
2012-08-24 |
Final Order |
2013-03-13 |
Nr Instances |
1 |
Nr Exposed |
4 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use: a) On or about 5/10/2012, Cleaning Chemical Storage Cage: Employees exposed to corrosive and caustic cleaning chemicals were not provided with an operable eye wash wear the chemicals were being dispensed. Abatement certification is required for this item. |
|
Citation ID |
01004A |
Citaton Type |
Serious |
Standard Cited |
19100147 C04 I |
Issuance Date |
2012-08-03 |
Abatement Due Date |
2012-08-10 |
Current Penalty |
3780.0 |
Initial Penalty |
6300.0 |
Contest Date |
2012-08-24 |
Final Order |
2013-03-13 |
Nr Instances |
5 |
Nr Exposed |
20 |
Gravity |
10 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.147(c)(4)(i): Procedures shall be developed, documented and utilized for the control of potentially hazardous energy when employees are engaged in the activities covered by this section. a) On or before 5/10/2012, Line#2: No lockout was being used while employees were cleaning the Topos Chunker. b) On or about 5/10/2012, Line #2: No lockout was being used while employees were cleaning and changing knife blades the Rounder. c) On or about 5/10/2012, Line #3: No lockout was being used while employees were changing the cutters (dies) on the dough cutting machines. d) On or about 5/10/2012, Throughout the facility: No lockout was being used while employees were cleaning mixers. e) On or about 5/10/2012, Throughout the facility: Specific energy control procedures were not developed and documented for the equipment in the facility. Equipment had energy sources such as, but not limited to gas, electric, potential, steam, and pneumatic energies. Abatement documentation is required for this item. |
|
Citation ID |
01004B |
Citaton Type |
Serious |
Standard Cited |
19100147 F03 I |
Issuance Date |
2012-08-03 |
Abatement Due Date |
2012-08-10 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Contest Date |
2012-08-24 |
Final Order |
2013-03-13 |
Nr Instances |
1 |
Nr Exposed |
5 |
Gravity |
10 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.147(f)(3)(i): A procedure was not utilized to afford the employees a level of protection equivalent to that provided by the implementation of a personal lockout or tagout device when servicing and/or maintenance was performed by a crew, craft, a) On or about 5/10/2012, Throughout the facility: When multiple people are performing work on equipment needing to be locked out, group lock out is not being utilized. Abatement documentation is required for this item. |
|
Citation ID |
01005A |
Citaton Type |
Serious |
Standard Cited |
19100147 C05 I |
Issuance Date |
2012-08-03 |
Abatement Due Date |
2012-08-10 |
Current Penalty |
0.0 |
Initial Penalty |
6300.0 |
Contest Date |
2012-08-24 |
Final Order |
2013-03-13 |
Nr Instances |
1 |
Nr Exposed |
20 |
Gravity |
10 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.147(c)(5)(i): Locks, tags, chains, wedges, key blocks, adapter pins, self-locking fasteners, or other hardware were not provided by the employer for isolating, securing or blocking of machines or equipment from energy sources: a) On or about 5/10/2012, Throughout the facility: Locks were not provided for all employees requiring to perform lock out functions. Abatement documentation is required for this item. |
|
Citation ID |
01005B |
Citaton Type |
Serious |
Standard Cited |
19100147 C05 II |
Issuance Date |
2012-08-03 |
Abatement Due Date |
2012-08-10 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Contest Date |
2012-08-24 |
Final Order |
2013-03-13 |
Nr Instances |
1 |
Nr Exposed |
20 |
Gravity |
10 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.147(c)(5)(ii): Lockout devices and tagout devices were not used for lockout and tagout purposes only: a) On or about 5/10/2012, Men's Locker Room: Lock out locks were being used in the men's locker room to secure lockers. Abatement documentation is required for this item. |
|
Citation ID |
01005C |
Citaton Type |
Serious |
Standard Cited |
19100147 C06 I |
Issuance Date |
2012-08-03 |
Abatement Due Date |
2012-08-10 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Contest Date |
2012-08-24 |
Final Order |
2013-03-13 |
Nr Instances |
1 |
Nr Exposed |
20 |
Gravity |
10 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.147(c)(6)(i): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed: a) On or about 5/10/2012, Throughout the facility: No periodic inspection of the companies lock out program was conducted at least annually. Abatement documentation is required for this item. |
|
Citation ID |
01005D |
Citaton Type |
Serious |
Standard Cited |
19100147 C07 I |
Issuance Date |
2012-08-03 |
Abatement Due Date |
2012-08-10 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Contest Date |
2012-08-24 |
Final Order |
2013-03-13 |
Nr Instances |
1 |
Nr Exposed |
20 |
Gravity |
10 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.147(c)(7)(i): The employer did not provide adequate training to ensure that the purpose and function of the energy control program was understood by employees: a) On or about 5/10/2012, Throughout the facility: Training was not provided for all employees that needed to utilize lock out and to all employees that would be effected by lock out activities. Abatement documentation is required for this item. |
|
Citation ID |
01006 |
Citaton Type |
Serious |
Standard Cited |
19100176 B |
Issuance Date |
2012-08-03 |
Abatement Due Date |
2012-08-10 |
Current Penalty |
2700.0 |
Initial Penalty |
4500.0 |
Contest Date |
2012-08-24 |
Final Order |
2013-03-13 |
Nr Instances |
1 |
Nr Exposed |
4 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.176(b): Storage of material created a hazard: a) On or about 5/10/2012, Main Holding Freezer: Numerous structural members on the storage racking were damaged. Abatement certification is required for this item. |
|
Citation ID |
01007A |
Citaton Type |
Serious |
Standard Cited |
19100212 A01 |
Issuance Date |
2012-08-03 |
Abatement Due Date |
2012-08-10 |
Current Penalty |
2160.0 |
Initial Penalty |
3600.0 |
Contest Date |
2012-08-24 |
Final Order |
2013-03-13 |
Nr Instances |
8 |
Nr Exposed |
20 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks: a) On or about 5/10/2012, Line#1: Pinch points on the Hobart Adamatic Sheeter were not guarded. b) On or about 5/10/2012, Line#1: Pinch points at the rear of the Hobart Divider was not guarded. c) On or about 5/10/2012, Line#1: Pinch points on the conveyor near the metal detector were not guarded. d) On or about 5/10/2012, Line#1: Pinch points created by the bottom of the blue Hanover conveyor were not guarded. e) On or about 5/10/2012, Line#2: Pinch points were not guarded on the Rounder. f) On or about 5/10/2012, Line#2: Pinch points on the bottom of the upper conveyor from the freezer were not guarded. g) On or about 5/10/2012, Line#4: A pinch point on the Benier Roller was not guarded. h) On or about 5/10/2012, Gluten Free Area: A pinch point on the packing conveyor was not guarded. Abatement certification is required for this item. |
|
Citation ID |
01007B |
Citaton Type |
Serious |
Standard Cited |
19100263 I07 I |
Issuance Date |
2012-08-03 |
Abatement Due Date |
2012-08-10 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Contest Date |
2012-08-24 |
Final Order |
2013-03-13 |
Nr Instances |
1 |
Nr Exposed |
4 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.263(i)(7)(i): Underside(s) of conveyor(s) were not completely enclosed where they passed over a main aisle way, regularly occupied work area, or passageway to prevent broken chains or other material from falling: a) On or about 5/10/2012, Line#2: The overhead conveyor exiting the spiral freezer did not contain the frozen dough balls. Abatement certification is required for this item. |
|
Citation ID |
01008A |
Citaton Type |
Serious |
Standard Cited |
19100219 C03 |
Issuance Date |
2012-08-03 |
Abatement Due Date |
2012-08-10 |
Current Penalty |
1620.0 |
Initial Penalty |
2700.0 |
Contest Date |
2012-08-24 |
Final Order |
2013-03-13 |
Nr Instances |
1 |
Nr Exposed |
2 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.219(c)(3): Vertical or inclined shafting seven -7 feet or less from floor or working platform was not enclosed with stationary casing(s) a) On or about 5/10/2012, Line #2: The Rounder had an unguarded vertical shaft at the flour indexer. Abatement certification is required for this item. |
|
Citation ID |
01008B |
Citaton Type |
Serious |
Standard Cited |
19100219 C04 I |
Issuance Date |
2012-08-03 |
Abatement Due Date |
2012-08-10 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Contest Date |
2012-08-24 |
Final Order |
2013-03-13 |
Nr Instances |
3 |
Nr Exposed |
20 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.219(c)(4)(i): Unguarded projecting shaft end(s) did not present a smooth edge and end and projected more than one half the diameter of the shaft: a) On or about 5/10/2012, Line #1: A Hobart Adamatic had a shaft end with projections. b) On or about 5/10/2012, Line #1: A Baldor DC Drive had a shaft end projecting with an exposed keyway. c) On or about 5/10/2012, Line #1: A Lesson Motor had a projecting shaft end with an exposed keyway. Abatement certification is required for this item. |
|
Citation ID |
01009A |
Citaton Type |
Serious |
Standard Cited |
19100219 D01 |
Issuance Date |
2012-08-03 |
Abatement Due Date |
2012-08-10 |
Current Penalty |
2160.0 |
Initial Penalty |
3600.0 |
Contest Date |
2012-08-24 |
Final Order |
2013-03-13 |
Nr Instances |
2 |
Nr Exposed |
5 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.219(d)(1): Pulley(s) with part(s) seven feet or less from the floor or work platform were not guarded in accordance with the requirements specified in 29 CFR 1910.219(m) and (o): a) On or about 5/10/2012, Flour Storage Area: Two pulleys were not provided with guards. b) On or about 5/10/2012, Line#2: Three Pulleys were not guarded on the Arpac Machine. Abatement certification is required for this item. |
|
Citation ID |
01009B |
Citaton Type |
Serious |
Standard Cited |
19100219 E01 I |
Issuance Date |
2012-08-03 |
Abatement Due Date |
2012-08-10 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Contest Date |
2012-08-24 |
Final Order |
2013-03-13 |
Nr Instances |
2 |
Nr Exposed |
8 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.219(e)(1)(i): Horizontal belts which had both runs seven feet or less from the floor level were not guarded with a guard that extended to at least fifteen inches above the belt: a) On or about 5/10/2012, Flour Storage Area: Three Semi V belts were not provided with guards. b) On or about 5/10/2012, Line#2: A flat belt was not guarded on the Arpac Machine. Abatement certification is required for this item. |
|
Citation ID |
01009C |
Citaton Type |
Serious |
Standard Cited |
19100263 C03 |
Issuance Date |
2012-08-03 |
Abatement Due Date |
2012-08-10 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Contest Date |
2012-08-24 |
Final Order |
2013-03-13 |
Nr Instances |
2 |
Nr Exposed |
8 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.263(c)(3): Sprocket(s) and V-belt drive(s) of bakery machinery located within reach from platform(s) or passageway(s) or located within 8 feet 6 inches from the floor were not completely enclosed: a) On or about 5/10/2012, Line#2: Three Sprockets were not guarded on the Arpac Machine. b) On or about 5/10/2012, Line #4: A Sprocket for the guide roller on the Spiral Cooling Conveyor was not guarded. Abatement certification is required for this item. |
|
Citation ID |
01010 |
Citaton Type |
Serious |
Standard Cited |
19100263 C08 |
Issuance Date |
2012-08-03 |
Abatement Due Date |
2012-08-10 |
Current Penalty |
1620.0 |
Initial Penalty |
2700.0 |
Contest Date |
2012-08-24 |
Final Order |
2013-03-13 |
Nr Instances |
1 |
Nr Exposed |
8 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.263(c)(8): Exposed hot water and steam pipes of bakery equipment were not covered with insulating material to protect employees from contact: a) On or about 5/10/2012, Line #4: The Steam Proofer had un insulated/ unprotected steam lines. Abatement certification is required for this item. |
|
Citation ID |
01011A |
Citaton Type |
Serious |
Standard Cited |
19100303 B01 |
Issuance Date |
2012-08-03 |
Abatement Due Date |
2012-08-10 |
Current Penalty |
2160.0 |
Initial Penalty |
3600.0 |
Contest Date |
2012-08-24 |
Final Order |
2013-03-13 |
Nr Instances |
3 |
Nr Exposed |
12 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.303(b)(1): Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees: a) On or about 5/10/2012, Line #2: The portable flour sifter had a damaged power cord. b) On or about 5/10/2012, Line #2 Arpac Packing Area: The conveyor power cord was damaged. c) On or about 5/10/2012, Line #4: A Panasonic induction motor had a damaged case. Abatement certification is required for this item. |
|
Citation ID |
01011B |
Citaton Type |
Serious |
Standard Cited |
19100305 G02 III |
Issuance Date |
2012-08-03 |
Abatement Due Date |
2012-08-10 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Contest Date |
2012-08-24 |
Final Order |
2013-03-13 |
Nr Instances |
4 |
Nr Exposed |
12 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws: a) On or about 5/10/2012, Flour Storage Area: The conduit was broken on the flour pump, no effective strain relief was present. b) On or about 5/10/2012, Line #2: The conduit was pulled out from the power supply to the Rounder, no effective strain relief was present. c) On or about 5/10/2012, Line #2 Arpac Packing Area: A motor case had the strain relief broken. d) On or about 5/10/2012, Line#3: The extruder had the sections of conduit pulled out, no effective strain relief was present. Abatement certification is required for this item. |
|
Citation ID |
01012 |
Citaton Type |
Serious |
Standard Cited |
19100303 F |
Issuance Date |
2012-08-03 |
Abatement Due Date |
2012-08-10 |
Current Penalty |
1620.0 |
Initial Penalty |
2700.0 |
Contest Date |
2012-08-24 |
Final Order |
2013-03-13 |
Nr Instances |
2 |
Nr Exposed |
20 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.303(f): Each service, feeder and branch circuit, at its disconnecting means or over current device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: a) On or about 5/10/2012, Line #4: Circuits were not labeled inside of two breaker boxes. b) On or about 5/10/2012, Gluten Free Area: Circuits were not labeled in a breaker box located on the South wall. Abatement certification is required for this item. |
|
Citation ID |
01013 |
Citaton Type |
Serious |
Standard Cited |
19100307 C |
Issuance Date |
2012-08-03 |
Abatement Due Date |
2012-08-10 |
Current Penalty |
2700.0 |
Initial Penalty |
4500.0 |
Contest Date |
2012-08-24 |
Final Order |
2013-03-13 |
Nr Instances |
2 |
Nr Exposed |
5 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.307(c): Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location: a) On or about 5/11/2012, Main Flour Storage Area: Electrical outlets near flour sifters and pumps were not intrinsically safe. b) On or about 5/11/2012, Main Flour Storage Area: A Craftsman shop vacuum was being used to clean up a large spill of flour. Abatement certification is required for this item. |
|
Citation ID |
01014A |
Citaton Type |
Serious |
Standard Cited |
19100332 B01 |
Issuance Date |
2012-08-03 |
Abatement Due Date |
2012-08-10 |
Current Penalty |
2700.0 |
Initial Penalty |
4500.0 |
Contest Date |
2012-08-24 |
Final Order |
2013-03-13 |
Nr Instances |
1 |
Nr Exposed |
4 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments: a) On or about 5/11/2012, Throughout the facility: Employees were required to perform troubleshooting work on energized equipment and energized circuits, without being trained in safety related work practices. Abatement certification is required for this item. |
|
Citation ID |
01014B |
Citaton Type |
Serious |
Standard Cited |
19100333 A01 |
Issuance Date |
2012-08-03 |
Abatement Due Date |
2012-08-10 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Contest Date |
2012-08-24 |
Final Order |
2013-03-13 |
Nr Instances |
1 |
Nr Exposed |
4 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.333(a)(1): Live parts to which an employee may be exposed were not de energized and locked out prior to employees working on or near them: a) On or about 5/11/2012, Throughout the facility: Employees were performing electrical work (non troubleshooting) on and near energized equipment without the use of safety related work practices. Abatement certification is required for this item. |
|
Citation ID |
01014C |
Citaton Type |
Serious |
Standard Cited |
19100335 A01 I |
Issuance Date |
2012-08-03 |
Abatement Due Date |
2012-08-10 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Contest Date |
2012-08-24 |
Final Order |
2013-03-13 |
Nr Instances |
1 |
Nr Exposed |
4 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed: a) On or about 5/11/2012, Throughout the facility: Employees performing troubleshooting work on energized equipment and energized circuits, were not wearing face, hand and body protection. Abatement certification is required for this item. |
|
Citation ID |
02001 |
Citaton Type |
Other |
Standard Cited |
19100305 G01 IV A |
Issuance Date |
2012-08-03 |
Abatement Due Date |
2012-08-10 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Contest Date |
2012-08-24 |
Final Order |
2013-03-13 |
Nr Instances |
1 |
Nr Exposed |
6 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: a) On or about 5/10/2012, Line #2: A conveyor was energized through an extension cord. Abatement certification is required for this item. |
|