Inspection Type |
Planned
|
Scope |
Complete
|
Safety/Health |
Safety
|
Close Conference |
2012-03-29
|
Emphasis |
L: FALL, L: LOCALTARG, N: CTARGET
|
Case Closed |
2017-06-28
|
Violation Items
Citation ID |
01001 |
Citaton Type |
Serious |
Standard Cited |
19260304 D |
Issuance Date |
2012-05-28 |
Current Penalty |
2400.0 |
Initial Penalty |
2400.0 |
Contest Date |
2012-06-25 |
Final Order |
2013-04-12 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1926.304(d): When the tool was withdrawn from the work, the lower guard did not automatically and instantly return to the covering position: a) At the jobsite, on or about 3/29/12: Employees were cutting vinyl siding with a Black and Decker Firestorm circular saw, the guard was pinned in the up position and did not cover the blade when cutting was complete. |
|
Citation ID |
01002A |
Citaton Type |
Serious |
Standard Cited |
19260404 F06 |
Issuance Date |
2012-05-28 |
Current Penalty |
1800.0 |
Initial Penalty |
1800.0 |
Contest Date |
2012-06-25 |
Final Order |
2013-04-12 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1926.404(f)(6): The path to ground from circuits, equipment, or enclosures was not permanent and continuous: a) At the jobsite, on or about 3/29/12: Employees were using an extension cord that was missing a ground pin. |
|
Citation ID |
01002B |
Citaton Type |
Serious |
Standard Cited |
19260404 B01 II |
Issuance Date |
2012-05-28 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Contest Date |
2012-06-25 |
Final Order |
2013-04-12 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1926.404(b)(1)(ii): On a construction site, where an assured equipment grounding program was not utilized, all 120-volt, single-phase, 15 and 20 ampere receptacle outlets which were not a part of the permanent wiring of the building or structure and which are in use by employees did not have approved ground fault circuit interrupers for personal protection: a) At the jobsite, on or about 3/29/12: The extension cord being used to power the Black and Decker Firestorm circular saw was not plugged into a GFCI. |
|
Citation ID |
01002C |
Citaton Type |
Serious |
Standard Cited |
19260416 E01 |
Issuance Date |
2012-05-28 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Contest Date |
2012-06-25 |
Final Order |
2013-04-12 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1926.416(e)(1): Worn or frayed electric cords or cables were used: a) At the jobsite, on or about 3/29/12: Employees were using an extension cord that was frayed at several locations, exposed the conductors to damage. |
|
Citation ID |
01003 |
Citaton Type |
Serious |
Standard Cited |
19260451 G01 |
Issuance Date |
2012-05-28 |
Current Penalty |
3000.0 |
Initial Penalty |
3000.0 |
Contest Date |
2012-06-25 |
Final Order |
2013-04-12 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1926.451(g)(1): Each employee on a scaffold more than 10 feet above a lower level were not protected from falling to that lower level: a) At the jobsite, on or about 3/29/12: An employee working from a scaffold was exposed to falls in excess of 10 feet without any means of fall protection. |
|
|