Inspection Type |
Complaint
|
Scope |
Partial
|
Safety/Health |
Health
|
Close Conference |
2019-09-19
|
Case Closed |
2020-12-04
|
Related Activity
Type |
Complaint |
Activity Nr |
1490332 |
Health |
Yes |
|
Type |
Inspection |
Activity Nr |
1432145 |
Safety |
Yes |
|
Violation Items
Citation ID |
01001 |
Citaton Type |
Serious |
Standard Cited |
19100141 A05 |
Issuance Date |
2020-01-28 |
Abatement Due Date |
2020-12-04 |
Current Penalty |
570.0 |
Initial Penalty |
2892.0 |
Contest Date |
2020-02-19 |
Final Order |
2020-10-30 |
Nr Instances |
1 |
Nr Exposed |
2 |
Related Event Code (REC) |
Complaint |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.141(a)(5): Enclosed workplaces were not so constructed, equipped, and maintained to prevent the entrance or harborage of rodents, insects, or other vermin. A continuing and effective extermination program was not instituted where their presence was detected: a) On and before 9/19/2019, at facility, for employees working at the establishment which were exposed to diseases directly or indirectly transmitted by rodents such as salmonella and hantavirus. Rats or other vermin were not exterminated or controlled by the employer. |
|
Citation ID |
01002 |
Citaton Type |
Serious |
Standard Cited |
19101020 E02 I A |
Issuance Date |
2020-01-28 |
Abatement Due Date |
2020-11-30 |
Current Penalty |
580.0 |
Initial Penalty |
4048.0 |
Contest Date |
2020-02-19 |
Final Order |
2020-10-30 |
Nr Instances |
1 |
Nr Exposed |
1 |
Related Event Code (REC) |
Complaint |
Gravity |
10 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.1020(e)(2)(i)(A): The employer did not, upon request, ensure each employee and designated representative access to employee exposure records, defined in 29 CFR 1910.1020(e)(2)(i)(A)(1)-(3) as relevant to employee exposure: a) On or about 10/2/2019, at facility, following an incident involving Fiberlock Technologies Fiberspray Airless Spray Encapsulant, an asbestos abatement product, the safety data sheet was not provided to the injured employee as an exposure record for his physician. |
|
Citation ID |
01003A |
Citaton Type |
Serious |
Standard Cited |
19101200 E01 |
Issuance Date |
2020-01-28 |
Abatement Due Date |
2020-12-04 |
Current Penalty |
570.0 |
Initial Penalty |
2892.0 |
Contest Date |
2020-02-19 |
Final Order |
2020-10-30 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.1200(e)(1): Employer did not develop, implement, and maintain at each workplace, a written hazard communication program which at least describes how the criteria specified in paragraphs (f), (g), and (h) of this section for labels and other forms of warning, safety data sheets, and employee information and training will be met, and which also includes the following: (a) On or about 10/2/2019, at facility, for the store manager exposed to Fiberlock Technologies Fiberspray Airless Spray Encapsulant, an asbestos abatement product. Employer did not develop a hazard communication program. |
|
Citation ID |
01003B |
Citaton Type |
Serious |
Standard Cited |
19101200 G08 |
Issuance Date |
2020-01-28 |
Abatement Due Date |
2020-12-04 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Contest Date |
2020-02-19 |
Final Order |
2020-10-30 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.1200(g)(8): The employer did not maintain in the workplace copies of the required safety data sheets for each hazardous chemical, and did not ensure that they were readily accessible during each work shift to employees when they were in their work area(s): (a) On or about 10/2/2019, at facility, for the store manager exposed to Fiberlock Technologies Fiberspray Airless Spray Encapsulant, an asbestos abatement product. Employer did not have safety data sheets available. |
|
Citation ID |
01003C |
Citaton Type |
Serious |
Standard Cited |
19101200 H01 |
Issuance Date |
2020-01-28 |
Abatement Due Date |
2020-12-04 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Contest Date |
2020-02-19 |
Final Order |
2020-10-30 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.1200(h)(1): Employees were not provided effective information and training on hazardous chemicals in their work area at the time of their initial assignment and whenever a new hazard that the employees had not been previously trained about was introduced into their work area: (a) On or about 10/2/2019, at facility, for the store manager exposed to Fiberlock Technologies Fiberspray Airless Spray Encapsulant, an asbestos abatement product. Employer did not train employees on hazard communication. |
|
Citation ID |
01004 |
Citaton Type |
Serious |
Standard Cited |
19261101 E01 |
Issuance Date |
2020-01-28 |
Abatement Due Date |
2020-12-04 |
Current Penalty |
570.0 |
Initial Penalty |
2892.0 |
Contest Date |
2020-02-19 |
Final Order |
2020-10-30 |
Nr Instances |
1 |
Nr Exposed |
2 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1926.1101(e)(1): All Class I, II, and III asbestos work was not conducted within regulated areas: a) On or about 10/2/2019, in the boiler room, Class III asbestos work was done by encapsulating asbestos thermal system insulation (TSI) from existing pipes and TSI on the boiler. The employer did not establish a regulated area to minimize exposure to asbestos. |
|
Citation ID |
01005 |
Citaton Type |
Serious |
Standard Cited |
19261101 F02 I |
Issuance Date |
2020-01-28 |
Abatement Due Date |
2020-12-04 |
Current Penalty |
570.0 |
Initial Penalty |
2892.0 |
Contest Date |
2020-02-19 |
Final Order |
2020-10-30 |
Nr Instances |
1 |
Nr Exposed |
2 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1926.1101(f)(2)(i): The employer with a work operation covered by the asbestos standard did not ensure that a "competent person" conducted an exposure assessment immediately before or at the initiation of the operation to ascertain expected exposures during that operation or workplace: a) On or about 10/2/2019, in the boiler room, Class III asbestos work was done by encapsulating asbestos thermal system insulation (TSI) from existing pipes and TSI on the boiler. The employer did not perform an exposure assessment to determine accurately the airborne concentrations of asbestos to minimize exposure to asbestos. |
|
Citation ID |
01006 |
Citaton Type |
Serious |
Standard Cited |
19261101 G09 |
Issuance Date |
2020-01-28 |
Abatement Due Date |
2020-12-04 |
Current Penalty |
570.0 |
Initial Penalty |
2892.0 |
Contest Date |
2020-02-19 |
Final Order |
2020-10-30 |
Nr Instances |
1 |
Nr Exposed |
2 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1926.1101(g)(9): Class III asbestos work was not conducted using engineering and work practice controls which minimized the exposure to employees performing the asbestos work and to bystander employees: a) On or about 10/2/2019, in the boiler room, Class III asbestos work was done by encapsulating asbestos thermal system insulation (TSI) from existing pipes and TSI on the boiler. The employer did not perform work using engineering and work practice controls to minimize exposure to asbestos. |
|
Citation ID |
01007A |
Citaton Type |
Serious |
Standard Cited |
19261101 K01 II |
Issuance Date |
2020-01-28 |
Abatement Due Date |
2020-12-04 |
Current Penalty |
570.0 |
Initial Penalty |
2892.0 |
Contest Date |
2020-02-19 |
Final Order |
2020-10-30 |
Nr Instances |
1 |
Nr Exposed |
2 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1926.1101(k)(1)(ii): The employer did not include asbestos in the program established to comply with the Hazard Communication Standard (HCS) and ensure each employee was trained in accordance with the provisions of the HCS and paragraphs (k)(9) and (10) of this section. The employer did not provide information on at least the following hazards: Cancer and lung effects. a) On or about 10/2/2019, in the boiler room, Class III asbestos work was done by encapsulating asbestos thermal system insulation (TSI) from existing pipes and TSI on the boiler. The employer did not train the employees on the hazards of asbestos. The employees told the owner about the poor condition of the asbestos in the boiler room. |
|
Citation ID |
01007B |
Citaton Type |
Serious |
Standard Cited |
19261101 K02 I |
Issuance Date |
2020-01-28 |
Abatement Due Date |
2020-12-04 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Contest Date |
2020-02-19 |
Final Order |
2020-10-30 |
Nr Instances |
1 |
Nr Exposed |
2 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1926.1101(k)(2)(i): Before work subject to this standard began, the building and/or facility owner(s) did not determine the presence, location and quantity of asbestos containing material (ACM) and/or presumed asbestos containing material (PACM) at the worksite pursuant to 29 CFR 1926.1101(k)(1): a) On or about 10/2/2019, in the boiler room, for the store manager that went in the room to check the water meter and spray foam the exit door where there was damaged asbestos thermal system insulation (TSI) from existing pipes and TSI on the boiler. The employer did not identify the presence, location, and quantity of asbestos containing material. |
|
Citation ID |
01007C |
Citaton Type |
Serious |
Standard Cited |
19261101 K02 II B |
Issuance Date |
2020-01-28 |
Abatement Due Date |
2020-02-03 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Contest Date |
2020-02-19 |
Final Order |
2020-10-30 |
Nr Instances |
1 |
Nr Exposed |
2 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1926.1101(k)(2)(ii)(B): The building owner and/or facility owner did not notify employees of the owner who will work in or adjacent to areas containing asbestos containing material or presumed asbestos containing material of the presence, location and quantity: a) On or about 10/2/2019, in the boiler room, for the store manager that went in the room to check the water meter and spray foam the exit door where there was damaged asbestos thermal system insulation (TSI) from existing pipes and TSI on the boiler. The employer did not train the employees on the hazards presence, location, and quantity of asbestos in the workplace. |
|
Citation ID |
01007D |
Citaton Type |
Serious |
Standard Cited |
19261101 K08 VII |
Issuance Date |
2020-01-28 |
Abatement Due Date |
2020-02-03 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Contest Date |
2020-02-19 |
Final Order |
2020-10-30 |
Nr Instances |
1 |
Nr Exposed |
2 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1926.1101(k)(8)(vii): Labels or signs were not affixed or posted so that employees will be notified of what materials contain PACM and/or ACM: a) On or about 10/2/2019, in the boiler room, for the store manager that went in the room to check the water meter and spray foam the exit door where there was damaged asbestos thermal system insulation (TSI) from existing pipes and TSI on the boiler. The employer did not notify employees of what materials contain PACM and/or ACM to minimize exposure to asbestos by posting labels and signs as PACM and/or ACM. |
|
|
Inspection Type |
Complaint
|
Scope |
Partial
|
Safety/Health |
Safety
|
Close Conference |
2019-09-19
|
Case Closed |
2020-12-30
|
Related Activity
Type |
Referral |
Activity Nr |
1510323 |
Health |
Yes |
|
Type |
Complaint |
Activity Nr |
1490332 |
Health |
Yes |
|
Type |
Inspection |
Activity Nr |
1431943 |
Health |
Yes |
|
Violation Items
Citation ID |
01001A |
Citaton Type |
Serious |
Standard Cited |
19100022 A01 |
Issuance Date |
2020-01-28 |
Abatement Due Date |
2020-11-04 |
Current Penalty |
250.0 |
Initial Penalty |
1735.0 |
Contest Date |
2020-02-19 |
Final Order |
2020-10-30 |
Nr Instances |
3 |
Nr Exposed |
2 |
Related Event Code (REC) |
Complaint |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.22(a)(1): All places of employment, passageways, storerooms, service rooms, and walking-working surfaces were not kept in a clean, orderly, and sanitary condition: a) Storage Room that leads to Boiler Room - On or prior to September 19, 2019, the storage room that leads to the boiler room was not kept in a clean, orderly, or sanitary condition with this storage room filled with materials and full of clutter. b) Boiler Room - On or prior to September 19, 2019, the boiler room was not kept in a clean, orderly, or sanitary condition with the boiler room filled with materials and full of clutter. c) Store Room Floor - On or prior to September 19, 2019, the store was not kept in a clean, orderly, or sanitary condition with the store room floor/carpeting having a musty smell with an observed rodent running in the store presenting potential cleanliness and sanitary hazards, and the carpeting being ripped/torn presenting potential trip hazards. |
|
Citation ID |
01001B |
Citaton Type |
Serious |
Standard Cited |
19100176 C |
Issuance Date |
2020-01-28 |
Abatement Due Date |
2020-11-04 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Contest Date |
2020-02-19 |
Final Order |
2020-10-30 |
Nr Instances |
3 |
Nr Exposed |
2 |
Related Event Code (REC) |
Complaint |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.176(c): Storage areas were not kept free from accumulation of materials that constituted hazards from tripping, fire, explosion or pest harborage: a) Storage Room that leads to Boiler Room - On or prior to September 19, 2019, the storage room that leads to the boiler room was not kept in a clean, orderly, or sanitary condition with this storage room filled with materials and full of clutter resulting in tripping, fire, and pest harborage hazards. b) Boiler Room - On or prior to September 19, 2019, the boiler room was not kept in a clean, orderly, or sanitary condition with the boiler room filled with materials and full of clutter resulting in tripping, fire, and pest harborage hazards. c) Store Room Floor - On or prior to September 19, 2019, the store was not kept in a clean, orderly, or sanitary condition with the store room floor/carpeting having a musty smell with an observed rodent running in the store presenting potential cleanliness and sanitary hazards, and the carpeting being ripped/torn resulting in tripping, fire, and pest harborage hazards. |
|
Citation ID |
01002 |
Citaton Type |
Serious |
Standard Cited |
19100022 A03 |
Issuance Date |
2020-01-28 |
Abatement Due Date |
2020-11-04 |
Current Penalty |
250.0 |
Initial Penalty |
1735.0 |
Contest Date |
2020-02-19 |
Final Order |
2020-10-30 |
Nr Instances |
1 |
Nr Exposed |
1 |
Related Event Code (REC) |
Complaint |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.22(a)(3): Walking-working surfaces were not maintained free of hazards such as sharp or protruding objects, loose boards, corrosion, leaks, spills, snow, and ice: a) Store Room Floor - On or prior to September 19, 2019, an old lift with 4 bolts approximately 2 inches in height created a trip hazard for employees that walk through the store. |
|
Citation ID |
01003A |
Citaton Type |
Serious |
Standard Cited |
19100036 D01 |
Issuance Date |
2020-01-28 |
Abatement Due Date |
2020-11-04 |
Current Penalty |
450.0 |
Initial Penalty |
4048.0 |
Contest Date |
2020-02-19 |
Final Order |
2020-10-30 |
Nr Instances |
2 |
Nr Exposed |
2 |
Related Event Code (REC) |
Complaint |
Gravity |
10 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.36(d)(1): Employee(s) were not able to open an exit route door from the inside at all times without keys, tools, or special knowledge: a) Boiler Room - On or prior to September 19, 2019, an exit door was spray foamed shut. Employees were unable to open the exit door without using tools to remove the spray foam insulation. b) Front of Store - On or prior to September 19, 2019, an exit door did not have a handle on the inside of the door, and the exit door was propped open by a string. In the event the exit door was closed, employees would not be able to open the door from the inside. |
|
Citation ID |
01003B |
Citaton Type |
Serious |
Standard Cited |
19100037 A03 |
Issuance Date |
2020-01-28 |
Abatement Due Date |
2020-11-04 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Contest Date |
2020-02-19 |
Final Order |
2020-10-30 |
Nr Instances |
3 |
Nr Exposed |
2 |
Related Event Code (REC) |
Complaint |
Gravity |
10 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed: a) Storage Room that leads to the Boiler Room and the Boiler Room - On or prior to September 19, 2019, an exit route was not kept free and unobstructed with various materials and clutter stored in the exit route and in front of the exit door. b) Long Hallway - On or prior to September 19, 2019, an exit route was not kept free and unobstructed with boxes, a trash bin, and other materials stored in an exit route leaving a space of approximately 10 inches of access. c) Boiler Room - On or prior to September 19, 2019, the boiler room was not kept free and unobstructed with the boiler room being filled with materials and full of clutter directly in front of the exit route door. The exit door was also sealed shut by spray foam insulation. |
|
Citation ID |
01003C |
Citaton Type |
Serious |
Standard Cited |
19100037 A04 |
Issuance Date |
2020-01-28 |
Abatement Due Date |
2020-11-04 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Contest Date |
2020-02-19 |
Final Order |
2020-10-30 |
Nr Instances |
2 |
Nr Exposed |
2 |
Related Event Code (REC) |
Complaint |
Gravity |
10 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.37(a)(4): Safeguard(s) designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting), were not in proper working order at all times: a) Boiler Room - On or prior to September 19, 2019, an exit door was spray foamed shut. Employees were unable to open the exit door due to the spray foam insulation sealing it shut. b) Front of Store - On or prior to September 19, 2019, an exit door did not have a handle on the inside of the door, and the exit door was propped open by a string. In the event the exit door was closed, employees would not be able to open the door from the inside. |
|
Citation ID |
01004A |
Citaton Type |
Serious |
Standard Cited |
19100037 B01 |
Issuance Date |
2020-01-28 |
Abatement Due Date |
2020-11-04 |
Current Penalty |
450.0 |
Initial Penalty |
4048.0 |
Contest Date |
2020-02-19 |
Final Order |
2020-10-30 |
Nr Instances |
1 |
Nr Exposed |
2 |
Related Event Code (REC) |
Complaint |
Gravity |
10 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.37(b)(1): Each exit route was not adequately lighted so that an employee with normal vision can see along the exit route: a) Store - On or prior to September 19, 2019, the store did not contain emergency lighting for employees to safely exit the building when closing the store for the night and/or if there were an emergency situation. |
|
Citation ID |
01004B |
Citaton Type |
Serious |
Standard Cited |
19100037 B02 |
Issuance Date |
2020-01-28 |
Abatement Due Date |
2020-11-04 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Contest Date |
2020-02-19 |
Final Order |
2020-10-30 |
Nr Instances |
1 |
Nr Exposed |
2 |
Related Event Code (REC) |
Complaint |
Gravity |
10 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit": a) Boiler Room - On or prior to September 19, 2019, there was not an exit sign posted above the exit door in the Boiler Room. |
|
Citation ID |
01004C |
Citaton Type |
Serious |
Standard Cited |
19100037 B06 |
Issuance Date |
2020-01-28 |
Abatement Due Date |
2020-11-04 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Contest Date |
2020-02-19 |
Final Order |
2020-10-30 |
Nr Instances |
2 |
Nr Exposed |
2 |
Related Event Code (REC) |
Complaint |
Gravity |
10 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.37(b)(6): Each exit sign was not illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color: a) Front of Store - On or prior to September 19, 2019, an exit sign was not illuminated. b) Long Hallway - On or about September 19, 2019, an exit sign was not illuminated. |
|
Citation ID |
01005A |
Citaton Type |
Serious |
Standard Cited |
19100303 B02 |
Issuance Date |
2020-01-28 |
Abatement Due Date |
2020-02-03 |
Current Penalty |
350.0 |
Initial Penalty |
2892.0 |
Contest Date |
2020-02-19 |
Final Order |
2020-10-30 |
Nr Instances |
2 |
Nr Exposed |
2 |
Related Event Code (REC) |
Complaint |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) Store - On or prior to September 19, 2019, the employer was using a relocatable power tap (RPT) or power strip which is not designed for industrial use to power a refrigerator, fan, and a heater (when it is cold out). This RPT was plugged into an extension cord. b) Computer Desk by Long Hallway - On or prior to September 19, 2019, a relocatable power tap (RPT) or power strip powering various equipment was not installed and used in accordance with instruction in the listing, labeling, or certification such as, but not limited to, being permanently secured to the desk with being plugged into an extension cord used as a substitute for fixed wiring. |
|
Citation ID |
01005B |
Citaton Type |
Serious |
Standard Cited |
19100305 G01 IV A |
Issuance Date |
2020-01-28 |
Abatement Due Date |
2020-02-03 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Contest Date |
2020-02-19 |
Final Order |
2020-10-30 |
Nr Instances |
2 |
Nr Exposed |
2 |
Related Event Code (REC) |
Complaint |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: a) Store - On or prior to September 19, 2019, the employer was using a relocatable power tap (RPT) or power strip which is not designed for industrial use to power a refrigerator, fan, and heater. This RPT was plugged into an extension cord. The extension cord was used as a substitute for fixed wiring. b) Computer Desk by Long Hallway - On or prior to September 19, 2019, a relocatable power tap (RPT) or power strip powering various equipment was not installed and used in accordance with instruction in the listing, labeling, or certification such as, but not limited to, being permanently secured to the desk with being plugged into an extension cord used as a substitute for fixed wiring. |
|
Citation ID |
01005C |
Citaton Type |
Serious |
Standard Cited |
19100305 G01 IV C |
Issuance Date |
2020-01-28 |
Abatement Due Date |
2020-02-03 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Contest Date |
2020-02-19 |
Final Order |
2020-10-30 |
Nr Instances |
1 |
Nr Exposed |
2 |
Related Event Code (REC) |
Complaint |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.305(g)(1)(iv)(C): Flexible cords and cables were run through doorways, windows, floors, or similar openings: a) Storage Room with Lamps - On or prior to September 19, 2019 an extension cord was plugged into a relocatable power tap (RPT) or power strip powering a refrigerator, computer, lamp, and fan was run through a doorway. |
|
Citation ID |
01006 |
Citaton Type |
Serious |
Standard Cited |
19100305 B01 II |
Issuance Date |
2020-01-28 |
Abatement Due Date |
2020-02-03 |
Current Penalty |
250.0 |
Initial Penalty |
1735.0 |
Contest Date |
2020-02-19 |
Final Order |
2020-10-30 |
Nr Instances |
1 |
Nr Exposed |
1 |
Related Event Code (REC) |
Complaint |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: a) Store - On or prior to September 19, 2019, three electrical boxes with switches that controlled the lights had unused openings exposing an employee to electrical hazards due to having to turn the lights on/off every day. b) Store - On or prior to September 19, 2019, an electrical box located below the three electrical boxes with switches that controlled the lights was completely open exposing an employee to electrical hazards due to having to turn the lights on/off every day using the three electrical boxes with switches. c) Store - On or prior to September 19, 2019, an electrical panel box located to the left of the three electrical boxes with switches that controlled the lights had a missing knockout. |
|
Citation ID |
02001 |
Citaton Type |
Other |
Standard Cited |
19100157 C01 |
Issuance Date |
2020-01-28 |
Abatement Due Date |
2020-02-03 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Contest Date |
2020-02-19 |
Final Order |
2020-10-30 |
Nr Instances |
2 |
Nr Exposed |
2 |
Related Event Code (REC) |
Complaint |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries: a) Long Hallway - On or about September 19, 2019, a portable fire extinguisher was blocked behind a box and bags of bottles and not mounted. b) Store - On or about September 19, 2019, a portable fire extinguisher was not mounted. |
|
Citation ID |
02002 |
Citaton Type |
Other |
Standard Cited |
19100157 C04 |
Issuance Date |
2020-01-28 |
Abatement Due Date |
2020-02-03 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Contest Date |
2020-02-19 |
Final Order |
2020-10-30 |
Nr Instances |
1 |
Nr Exposed |
2 |
Related Event Code (REC) |
Complaint |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.157(c)(4): Portable fire extinguishers were not maintained in a fully charged and operable condition: a) Store - On or about September 19, 2019, a portable fire extinguisher was not fully charged. |
|
Citation ID |
02003 |
Citaton Type |
Other |
Standard Cited |
19100303 F02 |
Issuance Date |
2020-01-28 |
Abatement Due Date |
2020-02-03 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Contest Date |
2020-02-19 |
Final Order |
2020-10-30 |
Nr Instances |
1 |
Nr Exposed |
1 |
Related Event Code (REC) |
Complaint |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: a) Store - On or prior to September 19, 2019, an electrical panel was not labeled. |
|
Citation ID |
02004 |
Citaton Type |
Other |
Standard Cited |
19100303 G01 |
Issuance Date |
2020-01-28 |
Abatement Due Date |
2020-02-03 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Contest Date |
2020-02-19 |
Final Order |
2020-10-30 |
Nr Instances |
1 |
Nr Exposed |
2 |
Related Event Code (REC) |
Complaint |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: a) Boiler Room - On or prior to September 19, 2019, materials were stored in front of electrical panels. |
|
|