Search icon

JUNE ELECTRIC CORP.

Company Details

Name: JUNE ELECTRIC CORP.
Jurisdiction: New York
Legal type: DOMESTIC BUSINESS CORPORATION
Status: Active
Date of registration: 20 Jun 2000 (25 years ago)
Entity Number: 2522980
ZIP code: 10461
County: Nassau
Place of Formation: New York
Address: 2025 CONTINENTAL AVE, STE #5E, BRONX, NY, United States, 10461

Shares Details

Shares issued 200

Share Par Value 0

Type NO PAR VALUE

DOS Process Agent

Name Role Address
RICH PAGANO DOS Process Agent 2025 CONTINENTAL AVE, STE #5E, BRONX, NY, United States, 10461

Chief Executive Officer

Name Role Address
RICH PAGANO Chief Executive Officer 2025 CONTINENTAL AVE, STE #5E, BRONX, NY, United States, 10461

History

Start date End date Type Value
2004-07-12 2006-06-02 Address 3110 WILKINSON AVE, BRONX, NY, 10461, USA (Type of address: Service of Process)
2004-07-12 2006-06-02 Address 3110 WILKINSON AVE, BRONX, NY, 10461, USA (Type of address: Principal Executive Office)
2004-07-12 2006-06-02 Address 3110 WILKINSON AVE, BRONX, NY, 10461, USA (Type of address: Chief Executive Officer)
2002-09-24 2004-07-12 Address 70 STRATHMORE RD, MANHASSET, NY, 11030, USA (Type of address: Chief Executive Officer)
2002-09-24 2004-07-12 Address 70 STRATHMORE RD, MANHASSET, NY, 11030, USA (Type of address: Principal Executive Office)
2002-09-24 2004-07-12 Address 70 STRATHMORE RD, MANHASSET, NY, 11030, USA (Type of address: Service of Process)
2000-06-20 2025-01-06 Shares Share type: NO PAR VALUE, Number of shares: 200, Par value: 0
2000-06-20 2002-09-24 Address 70 STRATHMORE ROAD, MANHASSET, NY, 11030, USA (Type of address: Service of Process)

Filings

Filing Number Date Filed Type Effective Date
080708003241 2008-07-08 BIENNIAL STATEMENT 2008-06-01
060602003221 2006-06-02 BIENNIAL STATEMENT 2006-06-01
040712002437 2004-07-12 BIENNIAL STATEMENT 2004-06-01
020924002150 2002-09-24 BIENNIAL STATEMENT 2002-06-01
000620000596 2000-06-20 CERTIFICATE OF INCORPORATION 2000-06-20

OSHA's Inspections within Industry

Inspection Nr Report ID Date Opened Site Address
340696582 0215000 2015-06-08 47-49 EAST 34TH ST., NEW YORK, NY, 10016
Inspection Type FollowUp
Scope Partial
Safety/Health Safety
Close Conference 2015-06-08
Case Closed 2015-07-07

Related Activity

Type Inspection
Activity Nr 862423
Safety Yes
338624232 0215000 2013-01-31 47 EAST 34TH ST., NEW YORK, NY, 10016
Inspection Type Referral
Scope Complete
Safety/Health Safety
Close Conference 2013-02-01
Case Closed 2018-08-28

Related Activity

Type Referral
Activity Nr 778732
Safety Yes

Violation Items

Citation ID 01001A
Citaton Type Serious
Standard Cited 19100332 B01
Issuance Date 2013-07-30
Abatement Due Date 2013-08-09
Current Penalty 3080.0
Initial Penalty 3080.0
Final Order 2013-08-23
Nr Instances 1
Nr Exposed 2
Gravity 10
FTA Current Penalty 0.0
Citation text line 29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments. a) Roof bulkhead electrical room: An employee was installing metal cover on an energized bus duct riser and was injured by an arc explosion. Injured employee was not trained in and familiar with the safety-related work practices that pertained to working on energized bus duct risers. On or about 01/31/13. NOTE: IN ADDITION TO CERTIFICATION OF ABATEMENT, THE EMPLOYER IS REQUIRED TO SUBMIT DOCUMENTATION OF ABATEMENT FOR THIS ITEM. FAILURE TO COMPLY MAY RESULT IN AN ADDITIONAL PENALTY OF $1,000 AS PER 29 CFR 1903.19.
Citation ID 01001B
Citaton Type Serious
Standard Cited 19100333 C02
Issuance Date 2013-07-30
Abatement Due Date 2013-08-09
Current Penalty 0.0
Initial Penalty 0.0
Final Order 2013-08-23
Nr Instances 1
Nr Exposed 2
Related Event Code (REC) Referral
Gravity 10
FTA Current Penalty 0.0
Citation text line 29 CFR 1910.333(c)(2): The employer did not ensure that only qualified persons were working on energized circuits and that qualified persons were familiar with the proper use of special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools. a) Roof bulkhead electrical room: An employee was installing metal cover on an energized bus duct riser and was injured by an arc explosion. Injured employee was not familiar with and not qualified to work on energized bus duct risers. The employer did not ensure only qualified employees were working on energized bus duct risers. On or about 01/31/13. NOTE: IN ADDITION TO CERTIFICATION OF ABATEMENT, THE EMPLOYER IS REQUIRED TO SUBMIT DOCUMENTATION OF ABATEMENT FOR THIS ITEM. FAILURE TO COMPLY MAY RESULT IN AN ADDITIONAL PENALTY OF $1,000 AS PER 29 CFR 1903.19.
Citation ID 01002
Citaton Type Serious
Standard Cited 19100333 A02
Issuance Date 2013-07-30
Abatement Due Date 2013-08-09
Current Penalty 3080.0
Initial Penalty 3080.0
Final Order 2013-08-23
Nr Instances 1
Nr Exposed 2
Related Event Code (REC) Referral
Gravity 10
FTA Current Penalty 0.0
Citation text line 29 CFR 1910.333(a)(2): Where exposed live parts were not de-energized, other safety related work practices were not used to protect employees who could be exposed to the electrical hazards involved. a) Roof bulkhead electrical room: An employee was installing metal cover on an energized bus duct riser and was injured by an arc explosion. Safety related work practices were not used to protect employees who were exposed to the electrical hazards involved in working on energized bus duct risers with exposed live parts. On or about 01/31/13. NOTE: IN ADDITION TO CERTIFICATION OF ABATEMENT, THE EMPLOYER IS REQUIRED TO SUBMIT DOCUMENTATION OF ABATEMENT FOR THIS ITEM. FAILURE TO COMPLY MAY RESULT IN AN ADDITIONAL PENALTY OF $1,000 AS PER 29 CFR 1903.19.
Citation ID 01003A
Citaton Type Serious
Standard Cited 19100335 A01 I
Issuance Date 2013-07-30
Abatement Due Date 2013-08-09
Current Penalty 3080.0
Initial Penalty 3080.0
Final Order 2013-08-23
Nr Instances 1
Nr Exposed 2
Related Event Code (REC) Referral
Gravity 10
FTA Current Penalty 0.0
Citation text line 29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed. a) Roof bulkhead electrical room: An employee was installing metal cover on an energized bus duct riser and was injured by an arc explosion. Injured employee was not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for working on energized bus duct risers. On or about 01/31/13. NOTE: IN ADDITION TO CERTIFICATION OF ABATEMENT, THE EMPLOYER IS REQUIRED TO SUBMIT DOCUMENTATION OF ABATEMENT FOR THIS ITEM. FAILURE TO COMPLY MAY RESULT IN AN ADDITIONAL PENALTY OF $1,000 AS PER 29 CFR 1903.19.
Citation ID 01003B
Citaton Type Serious
Standard Cited 19100335 A01 V
Issuance Date 2013-07-30
Abatement Due Date 2013-08-09
Current Penalty 0.0
Initial Penalty 0.0
Final Order 2013-08-23
Nr Instances 1
Nr Exposed 2
Related Event Code (REC) Referral
Gravity 10
FTA Current Penalty 0.0
Citation text line 29 CFR 1910.335(a)(1)(v): Employees exposed to the danger of injury to the eyes or face from electric arcs or flashes or from flying objects resulting from electrical explosion did not wear protective equipment for the eyes or face: a) Roof bulkhead electrical room: An employee was installing metal cover on an energized bus duct riser and suffered injuries to the eyes and face by an arc explosion. Injured employee was not provided with, and did not wear electrical protective equipment for the eyes and face. On or about 01/31/13. NOTE: IN ADDITION TO CERTIFICATION OF ABATEMENT, THE EMPLOYER IS REQUIRED TO SUBMIT DOCUMENTATION OF ABATEMENT FOR THIS ITEM. FAILURE TO COMPLY MAY RESULT IN AN ADDITIONAL PENALTY OF $1,000 AS PER 29 CFR 1903.19.
313004210 0216000 2010-08-11 850 JENNINGS AVENUE, BRONX, NY, 10459
Inspection Type Prog Related
Scope Complete
Safety/Health Safety
Close Conference 2010-08-12
Emphasis L: LOCALTARG, S: ELECTRICAL, S: RESIDENTIAL CONSTR
Case Closed 2014-01-24

Violation Items

Citation ID 01001
Citaton Type Serious
Standard Cited 19260025 A
Issuance Date 2010-09-22
Abatement Due Date 2010-10-15
Current Penalty 500.0
Initial Penalty 600.0
Nr Instances 1
Nr Exposed 2
Gravity 01
Citation ID 01002
Citaton Type Serious
Standard Cited 19260403 B02
Issuance Date 2010-09-22
Abatement Due Date 2010-10-15
Current Penalty 550.0
Initial Penalty 1000.0
Nr Instances 18
Nr Exposed 2
Gravity 03
Citation ID 01003
Citaton Type Serious
Standard Cited 19260405 B02
Issuance Date 2010-09-22
Abatement Due Date 2010-10-15
Current Penalty 550.0
Initial Penalty 1000.0
Nr Instances 2
Nr Exposed 3
Gravity 03
Citation ID 01004
Citaton Type Serious
Standard Cited 19261052 C01
Issuance Date 2010-09-22
Abatement Due Date 2010-09-27
Current Penalty 550.0
Initial Penalty 800.0
Nr Instances 2
Nr Exposed 2
Gravity 02
Citation ID 02001
Citaton Type Repeat
Standard Cited 19260405 A02 IIF
Issuance Date 2010-09-22
Abatement Due Date 2010-10-15
Current Penalty 1500.0
Initial Penalty 2000.0
Nr Instances 1
Nr Exposed 2
Gravity 03
Citation ID 02002
Citaton Type Repeat
Standard Cited 19260405 A02 IIE
Issuance Date 2010-09-22
Abatement Due Date 2010-09-27
Current Penalty 1500.0
Initial Penalty 2000.0
Nr Instances 15
Nr Exposed 2
Gravity 03
307667816 0216000 2005-08-19 941 & 951 HOE AVENUE, BRONX, NY, 10472
Inspection Type Prog Related
Scope Complete
Safety/Health Safety
Close Conference 2005-09-30
Case Closed 2005-12-13

Related Activity

Type Complaint
Activity Nr 205174634
Safety Yes

Violation Items

Citation ID 01001
Citaton Type Serious
Standard Cited 19260403 B01
Issuance Date 2005-09-30
Abatement Due Date 2005-10-05
Current Penalty 600.0
Initial Penalty 600.0
Nr Instances 1
Nr Exposed 1
Gravity 01
Citation ID 01002
Citaton Type Serious
Standard Cited 19260404 A02
Issuance Date 2005-09-30
Abatement Due Date 2005-10-05
Current Penalty 800.0
Initial Penalty 800.0
Nr Instances 1
Nr Exposed 1
Gravity 02
Citation ID 01003
Citaton Type Serious
Standard Cited 19260405 A02 IIE
Issuance Date 2005-09-30
Abatement Due Date 2005-10-05
Current Penalty 600.0
Initial Penalty 600.0
Nr Instances 1
Nr Exposed 1
Gravity 01
Citation ID 01004
Citaton Type Serious
Standard Cited 19260405 G01 III
Issuance Date 2005-09-30
Abatement Due Date 2005-10-05
Current Penalty 600.0
Initial Penalty 600.0
Nr Instances 1
Nr Exposed 1
Gravity 01
306251042 0215000 2002-12-10 1240 BEDFORD AVE, BROOKLYN, NY, 11216
Inspection Type Unprog Rel
Scope Complete
Safety/Health Safety
Close Conference 2002-12-11
Emphasis S: CONSTRUCTION
Case Closed 2003-10-20

Related Activity

Type Complaint
Activity Nr 204115067
Safety Yes

Violation Items

Citation ID 01001
Citaton Type Serious
Standard Cited 19260404 F06
Issuance Date 2003-01-22
Abatement Due Date 2003-01-30
Current Penalty 550.0
Initial Penalty 750.0
Nr Instances 8
Nr Exposed 4
Gravity 03
Citation ID 01002
Citaton Type Serious
Standard Cited 19260405 G02 IV
Issuance Date 2003-01-22
Abatement Due Date 2003-01-30
Current Penalty 550.0
Initial Penalty 750.0
Nr Instances 8
Nr Exposed 4
Gravity 03
304379175 0216000 2002-01-31 870 E. 162ND STREET, BRONX, NY, 10456
Inspection Type Prog Related
Scope Complete
Safety/Health Safety
Close Conference 2002-02-14
Emphasis S: CONSTRUCTION
Case Closed 2002-02-15

Date of last update: 30 Mar 2025