Inspection Type |
Planned
|
Scope |
Partial
|
Safety/Health |
Safety
|
Close Conference |
2023-06-01
|
Emphasis |
N: AMPUTATE, P: AMPUTATE
|
Case Closed |
2024-01-16
|
Violation Items
Citation ID |
01001 |
Citaton Type |
Serious |
Standard Cited |
19100147 C06 I |
Issuance Date |
2023-06-30 |
Current Penalty |
3000.0 |
Initial Penalty |
5313.0 |
Contest Date |
2023-07-24 |
Final Order |
2024-01-02 |
Nr Instances |
1 |
Nr Exposed |
3 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.147(c)(6)(i): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed: a) On or about 06/01/2023, throughout the establishment; where employees perform servicing and maintenance on machines and equipment such as but not limited to; the Holzma HPL 400 Saw, Homag CNC, Edge bander, table saw. The employer did not review the energy control program and procedures and each employee's responsibilities under the energy control procedure being inspected, at least annually. NO ABATEMENT CERTIFICATION REQUIRED |
|
Citation ID |
01002 |
Citaton Type |
Serious |
Standard Cited |
19100147 C07 I |
Issuance Date |
2023-06-30 |
Abatement Due Date |
2023-08-15 |
Current Penalty |
0.0 |
Initial Penalty |
5313.0 |
Contest Date |
2023-07-24 |
Final Order |
2024-01-02 |
Nr Instances |
1 |
Nr Exposed |
3 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.147(c)(7)(i): The employer did not provide training to ensure that the purpose and function of the energy control program are understood by employees and that the knowledge and skills required for the safe application, usage, and removal of the energy controls are acquired by employees: a) On or about 06/01/2023, throughout the establishment; Employer did not provide Lockout/Tagout (LOTO) training to all authorized and affected employees. Employees performed maintenance and servicing activities on machines such as, but not limited to: the Holzma HPL 400 Saw, Homag CNC, Edge bander, and table saw. ABATEMENT DOCUMENTATION REQUIRED |
|
|
Inspection Type |
Planned
|
Scope |
Partial
|
Safety/Health |
Safety
|
Close Conference |
2015-08-31
|
Emphasis |
N: AMPUTATE, N: DUSTEXPL, P: AMPUTATE
|
Case Closed |
2016-06-17
|
Violation Items
Citation ID |
01001 |
Citaton Type |
Serious |
Standard Cited |
5A0001 |
Issuance Date |
2015-10-26 |
Abatement Due Date |
2016-06-06 |
Current Penalty |
2000.0 |
Initial Penalty |
3500.0 |
Contest Date |
2015-11-17 |
Final Order |
2016-04-06 |
Nr Instances |
1 |
Nr Exposed |
6 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
OSH ACT of 1970 Section (5)(a)(1): The employer did not furnish employment and a place of employment which was free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to fire and explosion hazard; a) On or about 08/28/15 in the Beam Saw area; employer failed to protect employees from the fire and explosion hazard when two dust collectors for wood processing equipment, such as but not limited to, the Beam saw, CNC router, Edge bander, were located inside and without any fire prevention or suppression systems. ABATEMENT DOCUMENTATION REQUIRED National Fire Protection Association standard, NFPA 664 - 2012 Edition, Prevention of Fires and Explosions in Wood Processing and Woodworking Facilities, Section 8.2.2.5.1.4 requires; Dust collectors shall be located in accordance with one of the following: Among other methods, one feasible and acceptable abatement method to correct this hazardous condition would be, such as but not limited to; When dust collectors are located indoors; 1) Equip the dust collectors with a listed deflagration suppression system. 2) Equip the dust collectors with deflagration relief vents with relief pipes extending to safe areas outside of the building and verify the collectors met strength requirements of this standard. 3) Equip the dust collectors with deflagration relief vents exhausting through listed flame-quenching devices and verify the collectors met the strength requirements of this standard. |
|
Citation ID |
01002 |
Citaton Type |
Serious |
Standard Cited |
19100147 C04 I |
Issuance Date |
2015-10-26 |
Abatement Due Date |
2016-06-06 |
Current Penalty |
1200.0 |
Initial Penalty |
3500.0 |
Contest Date |
2015-11-17 |
Final Order |
2016-04-06 |
Nr Instances |
2 |
Nr Exposed |
2 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section: a) On or about 08/28/15 in the Beam Saw area; employer failed to protect employees from unexpected contact with a moving saw blade and product carriage when a procedure was not documented and utilized, to control hazardous energy (electric power and kinetic energy of rotating saw blade) during service and maintenance activities of the Beam Saw, such as but not limited to saw blade changing, cleaning dust accumulation, greasing the carriage rails of the beam saw. b) On or about 08/28/15 in the Edge Bander area; employer failed to protect employee from unexpected contact with moving parts of the Edge Bander when a procedure was not documented and utilized to control hazardous energy (pneumatic and electric power) during service and maintenance activities, such as but not limited to, unjamming, changing tooling, cleaning the internal parts of the edge bander. ABATEMENT CERTIFICATION REQUIRED |
|
Citation ID |
01003 |
Citaton Type |
Serious |
Standard Cited |
19100147 C07 I A |
Issuance Date |
2015-10-26 |
Abatement Due Date |
2016-06-06 |
Current Penalty |
1200.0 |
Initial Penalty |
3500.0 |
Contest Date |
2015-11-17 |
Final Order |
2016-04-06 |
Nr Instances |
2 |
Nr Exposed |
2 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.147(c)(7)(i)(A): Authorized employee(s) did not receive training in the recognition of applicable hazardous energy sources, the type and magnitude of the energy available in the workplace, and the methods and means necessary for energy isolation; a) On or about 08/28/15 in the Beam Saw area; employer failed to protect employees who performed service and maintenance activities, such as but not limited to saw blade changing, cleaning dust accumulation, greasing the carriage rails of the beam saw, from unexpected contact with a moving saw blade or product carriage movement, when they did not provide training about the methods and means for energy isolation and control prior to performing these tasks. b) On or about 08/28/15 in the Edge Bander area; employer failed to protect employee who performed service and maintenance activities, such as but not limited to, unjamming, changing tooling, cleaning the internal parts of the edge bander from unexpected contact with moving parts of the machine when they did not provide training about the methods and means for energy isolation and control prior to performing these tasks. ABATEMENT CERTIFICATION REQUIRED |
|
Citation ID |
01004A |
Citaton Type |
Serious |
Standard Cited |
19100147 D04 I |
Issuance Date |
2015-10-26 |
Abatement Due Date |
2016-06-06 |
Current Penalty |
1200.0 |
Initial Penalty |
3500.0 |
Contest Date |
2015-11-17 |
Final Order |
2016-04-06 |
Nr Instances |
2 |
Nr Exposed |
2 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.147(d)(4)(i): Lockout or tagout devices were not affixed to each energy isolating device by authorized employees: a) On or about 08/28/15 in the Beam Saw area; employer failed to protect employees from unexpected contact with a moving saw blade by not requiring the employee performing the blade changing on the beam saw to attach a lock or tag to the energy isolation devices. b) On or about 08/28/15 in the Edge Bander area; employer failed to protect employees from unexpected contact with moving parts of the edge bander machine by not requiring the employees performing, activities such as but not limited to unjamming, to attach a lock or tag to each of the energy isolation devices. ABATEMENT CERTIFICATION REQUIRED |
|
Citation ID |
01004B |
Citaton Type |
Serious |
Standard Cited |
19100147 F03 I |
Issuance Date |
2015-10-26 |
Abatement Due Date |
2016-06-06 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Contest Date |
2015-11-17 |
Final Order |
2016-04-06 |
Nr Instances |
1 |
Nr Exposed |
2 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.147(f)(3)(i): A procedure was not utilized to afford the employees a level of protection equivalent to that provided by the implementation of a personal lockout or tagout device when servicing and/or maintenance was performed by a crew, craft, a) On or about 08/28/15 in the Beam Saw area; employer failed to protect employees from unexpected contact with a moving saw blade when the only lock attached to the energy isolation device was that of an employee other than the one performing the blade changing on the beam saw. ABATEMENT CERTIFICATION REQUIRED |
|
Citation ID |
01005 |
Citaton Type |
Serious |
Standard Cited |
19100305 C04 |
Issuance Date |
2015-10-26 |
Current Penalty |
900.0 |
Initial Penalty |
2800.0 |
Contest Date |
2015-11-17 |
Final Order |
2016-04-06 |
Nr Instances |
1 |
Nr Exposed |
2 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.305(c)(4): Snap switches mounted in boxes did not have faceplates installed so as to completely cover the opening and seat against the finished surface. a) On or about 08/28/15 in the Parts Staging area; employer failed to protect employees against contact with electrical current ( 120 volts AC ) when the snap switch for the router did not have a cover. NO ABATEMENT CERTIFICATION REQUIRED |
|
|