346661424
|
0216000
|
2023-04-26
|
900 EDGEWATER ROAD, BRONX, NY, 10474
|
|
Inspection Type |
Planned
|
Scope |
NoInspection
|
Safety/Health |
Health
|
Close Conference |
2023-04-26
|
Emphasis |
N: PMETALS, N: SSTARG21, P: PMETALS
|
Case Closed |
2023-05-10
|
|
345648125
|
0216000
|
2021-11-18
|
900 EDGEWATER ROAD, BRONX, NY, 10474
|
|
Inspection Type |
Planned
|
Scope |
NoInspection
|
Safety/Health |
Health
|
Close Conference |
2021-11-18
|
Emphasis |
P: CHROME6, N: CHROME6
|
Case Closed |
2022-03-28
|
|
338146228
|
0216000
|
2013-01-07
|
900 EDGEWATER ROAD, BRONX, NY, 10474
|
|
Inspection Type |
Complaint
|
Scope |
Partial
|
Safety/Health |
Health
|
Close Conference |
2013-01-07
|
Case Closed |
2014-02-07
|
Related Activity
Type |
Complaint |
Activity Nr |
720731 |
Safety |
Yes |
Health |
Yes |
|
Violation Items
Citation ID |
01001A |
Citaton Type |
Serious |
Standard Cited |
19100036 D01 |
Issuance Date |
2013-01-25 |
Current Penalty |
1000.0 |
Initial Penalty |
2000.0 |
Final Order |
2013-03-01 |
Nr Instances |
1 |
Nr Exposed |
8 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.36(d)(1): Employee(s) were not able to open an exit route door from the inside at all times without keys, tools, or special knowledge: Location: Scale Room a) The rear exit door leading to the back scrap yard was locked; on or about 1/7/13. |
|
Citation ID |
01001B |
Citaton Type |
Serious |
Standard Cited |
19100037 A03 |
Issuance Date |
2013-01-25 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2013-03-01 |
Nr Instances |
1 |
Nr Exposed |
8 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed: Location: Scale Room a) The rear exit door leading to the back scrap yard was blocked by a metal plate; on or about 1/7/13. |
|
|
338178817
|
0216000
|
2013-01-07
|
900 EDGEWATER ROAD, BRONX, NY, 10474
|
|
Inspection Type |
Complaint
|
Scope |
Partial
|
Safety/Health |
Safety
|
Close Conference |
2013-01-07
|
Case Closed |
2013-07-02
|
Related Activity
Type |
Complaint |
Activity Nr |
720731 |
Safety |
Yes |
Health |
Yes |
|
Violation Items
Citation ID |
01001 |
Citaton Type |
Serious |
Standard Cited |
19100212 A03 II |
Issuance Date |
2013-01-31 |
Abatement Due Date |
2013-02-12 |
Current Penalty |
1000.0 |
Initial Penalty |
2000.0 |
Final Order |
2013-02-26 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.212(a)(3)(ii): Point(s) of operation of machinery were not guarded to prevent employee(s) from having any part of their body in the danger zone(s) during operating cycle(s): Location: 900 Edgewater Rd Bronx, NY 10474 On or about 1/7/13, a) The mesh guard for the baler had openings large enough to allow the operator to reach in and get caught by the machine during its operating cycle. |
|
Citation ID |
01002A |
Citaton Type |
Serious |
Standard Cited |
19100303 G02 I |
Issuance Date |
2013-01-31 |
Abatement Due Date |
2013-02-12 |
Current Penalty |
1000.0 |
Initial Penalty |
2000.0 |
Final Order |
2013-02-26 |
Nr Instances |
1 |
Nr Exposed |
9 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): Location: 900 Edgewater Rd Bronx, NY 10474 On or about 1/7/13, a) A circuit breaker panel was missing the front cover and door. Live parts were exposed. |
|
Citation ID |
01002B |
Citaton Type |
Serious |
Standard Cited |
19100305 B01 II |
Issuance Date |
2013-01-31 |
Abatement Due Date |
2013-02-12 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2013-02-26 |
Nr Instances |
1 |
Nr Exposed |
9 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: Location: 900 Edgewater Rd Bronx, NY 10474 On or about 1/7/13, a) There were several unused openings in a circuit breaker panel. |
|
Citation ID |
01003 |
Citaton Type |
Serious |
Standard Cited |
19100303 F02 |
Issuance Date |
2013-01-31 |
Abatement Due Date |
2013-02-12 |
Current Penalty |
600.0 |
Initial Penalty |
1200.0 |
Final Order |
2013-02-26 |
Nr Instances |
2 |
Nr Exposed |
9 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: Location: 900 Edgewater Rd Bronx, NY 10474 On or about 1/7/13, a) Two circuit breaker panels did not have all their circuit breakers marked. |
|
Citation ID |
01004 |
Citaton Type |
Serious |
Standard Cited |
19100304 F01 IV |
Issuance Date |
2013-01-31 |
Current Penalty |
600.0 |
Initial Penalty |
1200.0 |
Final Order |
2013-02-26 |
Nr Instances |
1 |
Nr Exposed |
8 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.304(f)(1)(iv): Overcurrent devices for circuits rated 600 volts, nominal, or less, were not readily accessible to each employee or authorized building management personnel: Location: 900 Edgewater Rd Bronx, NY 10474 On or about 1/7/13, a) A dumpster and a large container were blocking access to a circuit breaker panel. |
|
|