343333068
|
0213600
|
2018-07-27
|
1050 LEE ROAD, ROCHESTER, NY, 14606
|
|
Inspection Type |
Referral
|
Scope |
Partial
|
Safety/Health |
Safety
|
Close Conference |
2018-09-18
|
Emphasis |
N: AMPUTATE
|
Case Closed |
2019-03-11
|
Related Activity
Type |
Referral |
Activity Nr |
1361472 |
Safety |
Yes |
|
Violation Items
Citation ID |
01001A |
Citaton Type |
Serious |
Standard Cited |
19100147 C04 I |
Issuance Date |
2018-09-20 |
Current Penalty |
12934.0 |
Initial Penalty |
12934.0 |
Final Order |
2018-10-17 |
Nr Instances |
1 |
Nr Exposed |
3 |
Gravity |
10 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.147(c)(4)(i): Procedures were not utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section: a) On or about 07/19/18 On Line #6, Lee Road facility; employees were exposed to an amputation hazard when they crawled under the ABC Decaser and reached into the conveyor to clear multiple jams (7-8 jams within 20 minutes)of cardboard boxes and the employer did not require the use of the written ABC Decaser hazardous energy control procedure. NO ABATEMENT DOCUMENTATION REQUIRED |
|
Citation ID |
01001B |
Citaton Type |
Serious |
Standard Cited |
19100147 C07 I |
Issuance Date |
2018-09-20 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2018-10-17 |
Nr Instances |
1 |
Nr Exposed |
2 |
Gravity |
10 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.147(c)(7)(i): The employer did not provide adequate training to ensure that the purpose and function of the energy control program was understood by employees: a) On or about 07/19/18 On Line #6, Lee Road facility; employees were exposed to an amputation hazard while clearing multiple jams of cardboard boxes on the decaser when the employer training did not provide adequate information regarding when to implement the steps indicated in the control of hazardous energy procedure, i.e. preparation for shutdown, shutdown, isolation, application of control, verification of zero energy condition. NO ABATEMENT DOCUMENTATION REQURIED |
|
|
340892090
|
0213600
|
2015-09-03
|
1020 LEE ROAD, ROCHESTER, NY, 14606
|
|
Inspection Type |
FollowUp
|
Scope |
Partial
|
Safety/Health |
Safety
|
Close Conference |
2015-09-03
|
Case Closed |
2015-09-08
|
Related Activity
Type |
Inspection |
Activity Nr |
1017268 |
Safety |
Yes |
|
|
340172683
|
0213600
|
2015-01-14
|
1020 LEE ROAD, ROCHESTER, NY, 14606
|
|
Inspection Type |
Referral
|
Scope |
Partial
|
Safety/Health |
Safety
|
Close Conference |
2015-01-23
|
Case Closed |
2015-04-06
|
Related Activity
Type |
Referral |
Activity Nr |
931268 |
Health |
Yes |
|
Violation Items
Citation ID |
01001 |
Citaton Type |
Serious |
Standard Cited |
19100132 D01 I |
Issuance Date |
2015-02-04 |
Abatement Due Date |
2015-03-07 |
Current Penalty |
4290.0 |
Initial Penalty |
6600.0 |
Final Order |
2015-02-25 |
Nr Instances |
1 |
Nr Exposed |
10 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.132(d)(1)(i): The employer did not select and have each employee use, the types of personal protective equipment that would protect the affected employee(s) from the hazards identified in the hazard assessment: a) On or about 01/05/15 in the Line #3 area; employer failed to protect employee(s) from chemical flash and splash hazards to the face during the use of ZEP Cleaner ( R-12776 - corrosive ), when they only selected goggle use when handling this chemical. ABATEMENT DOCUMENTATION REQUIRED |
|
Citation ID |
01002 |
Citaton Type |
Serious |
Standard Cited |
19100151 C |
Issuance Date |
2015-02-04 |
Abatement Due Date |
2015-03-07 |
Current Penalty |
4290.0 |
Initial Penalty |
6600.0 |
Final Order |
2015-02-25 |
Nr Instances |
1 |
Nr Exposed |
10 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use: a) On or about 01/05/15 in the area near Line #3; employer failed to protect employees from chemical burns when handling ZEP brand R-12776 cleaner ( corrosive solid ) to clean the filler tank, when the two closest eye wash/safety shower locations were not adjacent to the hazard, they were located on the Kitchen Mezzanine and between Lines #1 & #2 near the labeler. ABATEMENT DOCUMENTATION REQUIRED |
|
|
332804152
|
0213600
|
2012-03-12
|
1020 LEE ROAD, ROCHESTER, NY, 14606
|
|
Inspection Type |
Complaint
|
Scope |
Partial
|
Safety/Health |
Safety
|
Close Conference |
2012-04-26
|
Case Closed |
2013-02-14
|
Related Activity
Type |
Complaint |
Activity Nr |
216281 |
Safety |
Yes |
|
Violation Items
Citation ID |
01001 |
Citaton Type |
Serious |
Standard Cited |
19100147 C04 II B |
Issuance Date |
2012-05-08 |
Abatement Due Date |
2012-06-22 |
Current Penalty |
5000.0 |
Initial Penalty |
5000.0 |
Contest Date |
2012-05-31 |
Final Order |
2012-11-15 |
Nr Instances |
1 |
Nr Exposed |
6 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.147(c)(4)(ii)(B): Specific procedural steps for shutting down, isolating, blocking and securing machines or equipment to control hazardous energy were not included; a) On or about 4/26/12 in the Palletizer area; Lockout-Tagout Procedure ID# L1-B1-Palletizer did not identify the hoist blocking mechanism ( cribing device ) as an energy source and this was not included in the LiDestri written lockout procedure. Abatement Certification |
|
Citation ID |
01002A |
Citaton Type |
Serious |
Standard Cited |
19100332 B01 |
Issuance Date |
2012-05-08 |
Abatement Due Date |
2012-06-22 |
Current Penalty |
4000.0 |
Initial Penalty |
4000.0 |
Contest Date |
2012-05-31 |
Final Order |
2012-11-15 |
Nr Instances |
2 |
Nr Exposed |
4 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments: (a) On or about 03/12/12 throughout the facililty; maintenance employees using voltage testing equipment on 480 volts AC, for activities such as but not limited to, trouble shooting equipment, checking voltage on electrical circuits, and were not provided training on the required protective equipment against arc flash hazards and use of this equipment during voltage testing. Abatement Certification |
|
Citation ID |
01002B |
Citaton Type |
Serious |
Standard Cited |
19100335 A01 I |
Issuance Date |
2012-05-08 |
Abatement Due Date |
2012-06-22 |
Current Penalty |
0.0 |
Initial Penalty |
4000.0 |
Contest Date |
2012-05-31 |
Final Order |
2012-11-15 |
Nr Instances |
1 |
Nr Exposed |
4 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed: (a) On or about 03/12/12 throughout the facilty; maintenance employees using voltage testing equipment on 480 volts circuits during equipment trouble shooting, were not provided with protective equiment, such as but not limited to voltage rated gloves, non melting clothing, arc rated flash shield to protect them against the hazards of arc flash/blast. Abatement Certification |
|
Citation ID |
02001A |
Citaton Type |
Repeat |
Standard Cited |
19100147 D03 |
Issuance Date |
2012-05-08 |
Abatement Due Date |
2012-06-22 |
Current Penalty |
0.0 |
Initial Penalty |
15000.0 |
Contest Date |
2012-05-31 |
Final Order |
2012-11-15 |
Nr Instances |
1 |
Nr Exposed |
6 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
LIDESTRI FOODS, INC. WAS PREVIOUSLY CITED FOR A VIOLATION OF THIS OCCUPATIONAL SAFETY AND HEALTH STANDARD OR ITS EQUIVALENT STANDARD, WHICH WAS CONTAINED IN OSHA INSPECTION NUMBER 314717307, CITATION NO. 1, ITEM NO. 3A , AND WAS AFFIRMED AS A FINAL ORDER ON 10/11/10, WITH RESPECT TO A WORKPLACE LOCATED AT 815 WEST WHITNEY ROAD, FAIRPORT, NEW YORK,14450 29 CFR 1910.147(d)(3): Machine or equipment isolation. All energy isolating devices that are needed to control the energy to the machine or equipment were not physically located and operated in such a manner as to isolate the machine or equipment from the energy source(s). a) On or about 4/26/12 in the Palletizer area; the three ball valves identified in Lockout-Tagout Procedure ID# L1-B1-Palletizer were not turned to the off position as part of the energy control methods prior to performing servicing and maintenance work, such as but not limited, to removal and clean up of crashed pallets. Abatement Documentation |
|
Citation ID |
02001B |
Citaton Type |
Repeat |
Standard Cited |
19100147 D04 I |
Issuance Date |
2012-05-08 |
Abatement Due Date |
2012-06-22 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Contest Date |
2012-05-31 |
Final Order |
2012-11-15 |
Nr Instances |
1 |
Nr Exposed |
6 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
LIDESTRI FOODS, INC. WAS PREVIOUSLY CITED FOR A VIOLATION OF THIS OCCUPATIONAL SAFETY AND HEALTH STANDARD OR ITS EQUIVALENT STANDARD, WHICH WAS CONTAINED IN OSHA INSPECTION NUMBER 314717307, CITATION NO. 1, ITEM NO. 3B , AND WAS AFFIRMED AS A FINAL ORDER ON 10/11/10, WITH RESPECT TO A WORKPLACE LOCATED AT 815 WEST WHITNEY ROAD, FAIRPORT, NEW YORK,14450 29 CFR 1910.147(d)(4)(i): Lockout or tagout devices shall be affixed to each energy isolating device by authorized employees. a) On or about 4/26/12 in the Palletizer area; locks were not affixed to the three ball valves as identified in Lockout-Tagout Procedure ID# L1-B1-Palletizer as part of the energy control methods prior to performing servicing and maintenance work, such as but not limited, to removal and clean up of crashed pallets. Abatement Certification |
|
|
315501114
|
0213600
|
2011-06-06
|
1020 LEE ROAD, ROCHESTER, NY, 14606
|
|
Inspection Type |
Referral
|
Scope |
Partial
|
Safety/Health |
Safety
|
Close Conference |
2011-06-30
|
Case Closed |
2011-08-24
|
Related Activity
Type |
Referral |
Activity Nr |
201339025 |
Safety |
Yes |
|
Violation Items
Citation ID |
01001A |
Citaton Type |
Serious |
Standard Cited |
19100147 C07 I |
Issuance Date |
2011-07-06 |
Abatement Due Date |
2011-07-24 |
Current Penalty |
3000.0 |
Initial Penalty |
6000.0 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
05 |
|
Citation ID |
01001B |
Citaton Type |
Serious |
Standard Cited |
19100147 C07 IIIC |
Issuance Date |
2011-07-06 |
Abatement Due Date |
2011-07-24 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
05 |
|
|
314717307
|
0213600
|
2010-08-03
|
815 WEST WHITNEY ROAD, FAIRPORT, NY, 14450
|
|
Inspection Type |
Planned
|
Scope |
Complete
|
Safety/Health |
Safety
|
Close Conference |
2010-09-09
|
Emphasis |
N: SSTARG09
|
Case Closed |
2010-10-27
|
Violation Items
Citation ID |
01001 |
Citaton Type |
Serious |
Standard Cited |
19100023 A08 |
Issuance Date |
2010-09-17 |
Abatement Due Date |
2010-10-20 |
Current Penalty |
800.0 |
Initial Penalty |
1125.0 |
Nr Instances |
2 |
Nr Exposed |
2 |
Gravity |
01 |
|
Citation ID |
01002 |
Citaton Type |
Other |
Standard Cited |
19100147 C06 IA |
Issuance Date |
2010-09-17 |
Abatement Due Date |
2010-10-20 |
Initial Penalty |
1875.0 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
03 |
|
Citation ID |
01003A |
Citaton Type |
Serious |
Standard Cited |
19100147 D03 |
Issuance Date |
2010-09-17 |
Abatement Due Date |
2010-10-20 |
Current Penalty |
4500.0 |
Initial Penalty |
4500.0 |
Nr Instances |
3 |
Nr Exposed |
4 |
Gravity |
10 |
|
Citation ID |
01003B |
Citaton Type |
Serious |
Standard Cited |
19100147 D04 I |
Issuance Date |
2010-09-17 |
Abatement Due Date |
2010-10-20 |
Nr Instances |
3 |
Nr Exposed |
4 |
Gravity |
10 |
|
Citation ID |
01004 |
Citaton Type |
Serious |
Standard Cited |
19100147 F03 IID |
Issuance Date |
2010-09-17 |
Abatement Due Date |
2010-10-20 |
Current Penalty |
4500.0 |
Initial Penalty |
4500.0 |
Nr Instances |
2 |
Nr Exposed |
2 |
Gravity |
10 |
|
Citation ID |
01005 |
Citaton Type |
Serious |
Standard Cited |
19100151 C |
Issuance Date |
2010-09-17 |
Abatement Due Date |
2010-10-20 |
Current Penalty |
1000.0 |
Initial Penalty |
1875.0 |
Nr Instances |
2 |
Nr Exposed |
1 |
Gravity |
03 |
|
Citation ID |
01006 |
Citaton Type |
Serious |
Standard Cited |
19100178 A04 |
Issuance Date |
2010-09-17 |
Abatement Due Date |
2010-10-20 |
Current Penalty |
1125.0 |
Initial Penalty |
1125.0 |
Nr Instances |
2 |
Nr Exposed |
2 |
Gravity |
01 |
|
Citation ID |
01007 |
Citaton Type |
Serious |
Standard Cited |
19100178 L06 |
Issuance Date |
2010-09-17 |
Abatement Due Date |
2010-09-22 |
Current Penalty |
1075.0 |
Initial Penalty |
1875.0 |
Nr Instances |
2 |
Nr Exposed |
2 |
Gravity |
04 |
|
Citation ID |
01008 |
Citaton Type |
Other |
Standard Cited |
19100212 A01 |
Issuance Date |
2010-09-17 |
Abatement Due Date |
2010-10-20 |
Initial Penalty |
1875.0 |
Nr Instances |
6 |
Nr Exposed |
2 |
Gravity |
03 |
|
Citation ID |
01009 |
Citaton Type |
Serious |
Standard Cited |
19100303 B01 I |
Issuance Date |
2010-09-17 |
Abatement Due Date |
2010-10-20 |
Current Penalty |
500.0 |
Initial Penalty |
1500.0 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
02 |
|
|
305232886
|
0213600
|
2002-07-10
|
815 WEST WHITNEY ROAD, FAIRPORT, NY, 14450
|
|
Inspection Type |
Referral
|
Scope |
Partial
|
Safety/Health |
Health
|
Close Conference |
2002-08-12
|
Emphasis |
S: FOOD PROCESSING, L: FOODPRO
|
Case Closed |
2003-08-22
|
Related Activity
Type |
Referral |
Activity Nr |
201333507 |
Health |
Yes |
|
Violation Items
Citation ID |
01001A |
Citaton Type |
Serious |
Standard Cited |
19100095 G06 |
Issuance Date |
2002-08-13 |
Abatement Due Date |
2002-08-16 |
Current Penalty |
2450.0 |
Initial Penalty |
3500.0 |
Nr Instances |
4 |
Nr Exposed |
4 |
Gravity |
05 |
|
Citation ID |
01001B |
Citaton Type |
Serious |
Standard Cited |
19100095 G08 IIB |
Issuance Date |
2002-08-13 |
Abatement Due Date |
2002-10-16 |
Nr Instances |
2 |
Nr Exposed |
2 |
Gravity |
05 |
|
Citation ID |
01001C |
Citaton Type |
Serious |
Standard Cited |
19100095 G08 IIC |
Issuance Date |
2002-08-13 |
Abatement Due Date |
2002-10-16 |
Nr Instances |
2 |
Nr Exposed |
2 |
Gravity |
05 |
|
Citation ID |
01001D |
Citaton Type |
Serious |
Standard Cited |
19100095 K01 |
Issuance Date |
2002-08-13 |
Abatement Due Date |
2002-12-16 |
Nr Instances |
4 |
Nr Exposed |
4 |
Gravity |
05 |
|
|
305163412
|
0213600
|
2002-03-28
|
815 WEST WHITNEY ROAD, FAIRPORT, NY, 14450
|
|
Inspection Type |
FollowUp
|
Scope |
Complete
|
Safety/Health |
Safety
|
Close Conference |
2002-08-12
|
Emphasis |
L: FOODPRO, S: FOOD PROCESSING
|
Case Closed |
2003-08-22
|
Related Activity
Type |
Inspection |
Activity Nr |
302864004 |
|
Violation Items
Citation ID |
01001 |
Citaton Type |
Serious |
Standard Cited |
19100029 F01 |
Issuance Date |
2002-08-13 |
Abatement Due Date |
2002-08-16 |
Current Penalty |
1750.0 |
Initial Penalty |
2500.0 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
04 |
|
Citation ID |
01002 |
Citaton Type |
Other |
Standard Cited |
19100037 Q05 |
Issuance Date |
2002-08-13 |
Abatement Due Date |
2002-09-16 |
Initial Penalty |
2000.0 |
Nr Instances |
6 |
Nr Exposed |
6 |
Gravity |
02 |
|
Citation ID |
01003 |
Citaton Type |
Serious |
Standard Cited |
19100133 A02 |
Issuance Date |
2002-08-13 |
Abatement Due Date |
2002-08-21 |
Current Penalty |
1750.0 |
Initial Penalty |
2500.0 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
03 |
|
Citation ID |
01004 |
Citaton Type |
Serious |
Standard Cited |
19100157 C01 |
Issuance Date |
2002-08-13 |
Abatement Due Date |
2002-08-21 |
Current Penalty |
2450.0 |
Initial Penalty |
3500.0 |
Nr Instances |
2 |
Nr Exposed |
7 |
Gravity |
05 |
|
Citation ID |
01005 |
Citaton Type |
Serious |
Standard Cited |
19100178 P01 |
Issuance Date |
2002-08-13 |
Abatement Due Date |
2002-08-16 |
Current Penalty |
1750.0 |
Initial Penalty |
2500.0 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
03 |
|
Citation ID |
01006 |
Citaton Type |
Serious |
Standard Cited |
19100212 A03 II |
Issuance Date |
2002-08-13 |
Abatement Due Date |
2002-10-16 |
Current Penalty |
3500.0 |
Initial Penalty |
5000.0 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
10 |
|
Citation ID |
01007 |
Citaton Type |
Serious |
Standard Cited |
19100303 G01 II |
Issuance Date |
2002-08-13 |
Abatement Due Date |
2002-08-21 |
Current Penalty |
1400.0 |
Initial Penalty |
2000.0 |
Nr Instances |
5 |
Nr Exposed |
4 |
Gravity |
02 |
|
Citation ID |
01008 |
Citaton Type |
Serious |
Standard Cited |
19101200 F05 |
Issuance Date |
2002-08-13 |
Abatement Due Date |
2002-08-21 |
Current Penalty |
2500.0 |
Initial Penalty |
2500.0 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
03 |
|
Citation ID |
01009 |
Citaton Type |
Serious |
Standard Cited |
19101200 H01 |
Issuance Date |
2002-08-13 |
Abatement Due Date |
2002-09-16 |
Current Penalty |
2500.0 |
Initial Penalty |
2500.0 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
03 |
|
Citation ID |
01010A |
Citaton Type |
Serious |
Standard Cited |
19101200 F05 |
Issuance Date |
2002-08-13 |
Abatement Due Date |
2002-08-21 |
Current Penalty |
1750.0 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
03 |
|
Citation ID |
01010B |
Citaton Type |
Serious |
Standard Cited |
19101200 H01 |
Issuance Date |
2002-08-13 |
Abatement Due Date |
2002-10-16 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
03 |
|
Citation ID |
02001 |
Citaton Type |
Serious |
Standard Cited |
19100147 C07 I |
Issuance Date |
2002-08-13 |
Abatement Due Date |
2002-08-21 |
Current Penalty |
5000.0 |
Initial Penalty |
25000.0 |
Nr Instances |
1 |
Nr Exposed |
100 |
Gravity |
10 |
|
Citation ID |
02002 |
Citaton Type |
Serious |
Standard Cited |
19100157 G02 |
Issuance Date |
2002-08-13 |
Abatement Due Date |
2002-08-21 |
Current Penalty |
5000.0 |
Initial Penalty |
25000.0 |
Nr Instances |
30 |
Nr Exposed |
2 |
Gravity |
10 |
|
|
302864004
|
0213600
|
2001-05-03
|
815 WEST WHITNEY ROAD, FAIRPORT, NY, 14450
|
|
Inspection Type |
Referral
|
Scope |
Partial
|
Safety/Health |
Safety
|
Close Conference |
2001-08-03
|
Case Closed |
2002-08-13
|
Related Activity
Type |
Referral |
Activity Nr |
201332749 |
Safety |
Yes |
|
Violation Items
Citation ID |
01001 |
Citaton Type |
Serious |
Standard Cited |
19100147 C04 I |
Issuance Date |
2001-08-10 |
Abatement Due Date |
2001-12-12 |
Current Penalty |
3150.0 |
Initial Penalty |
4500.0 |
Nr Instances |
2 |
Nr Exposed |
4 |
Related Event Code (REC) |
Referral |
Gravity |
10 |
|
Citation ID |
01002 |
Citaton Type |
Serious |
Standard Cited |
19100147 C06 I |
Issuance Date |
2001-08-10 |
Abatement Due Date |
2002-03-12 |
Current Penalty |
1530.0 |
Initial Penalty |
2250.0 |
Nr Instances |
6 |
Nr Exposed |
4 |
Gravity |
03 |
|
Citation ID |
01003 |
Citaton Type |
Serious |
Standard Cited |
19100147 C07 I |
Issuance Date |
2001-08-10 |
Abatement Due Date |
2001-09-12 |
Current Penalty |
1206.0 |
Initial Penalty |
1800.0 |
Nr Instances |
2 |
Nr Exposed |
4 |
Gravity |
02 |
|
Citation ID |
01004 |
Citaton Type |
Serious |
Standard Cited |
19100157 G02 |
Issuance Date |
2001-08-10 |
Abatement Due Date |
2001-09-12 |
Current Penalty |
908.0 |
Initial Penalty |
1350.0 |
Nr Instances |
30 |
Nr Exposed |
4 |
Gravity |
01 |
|
Citation ID |
02001 |
Citaton Type |
Other |
Standard Cited |
19040002 A |
Issuance Date |
2001-08-10 |
Abatement Due Date |
2001-08-14 |
Current Penalty |
1206.0 |
Initial Penalty |
1800.0 |
Nr Instances |
2 |
Gravity |
00 |
|
|
114096126
|
0213600
|
1994-11-30
|
815 WEST WHITNEY ROAD, FAIRPORT, NY, 14450
|
|
Inspection Type |
Complaint
|
Scope |
Partial
|
Safety/Health |
Safety
|
Close Conference |
1994-11-30
|
Case Closed |
1995-02-03
|
Related Activity
Type |
Complaint |
Activity Nr |
77164309 |
Safety |
Yes |
|
Violation Items
Citation ID |
01001 |
Citaton Type |
Serious |
Standard Cited |
19100147 C07 I |
Issuance Date |
1995-01-04 |
Abatement Due Date |
1995-01-13 |
Current Penalty |
472.5 |
Initial Penalty |
675.0 |
Nr Instances |
1 |
Nr Exposed |
2 |
Related Event Code (REC) |
Complaint |
Gravity |
01 |
|
Citation ID |
01002 |
Citaton Type |
Serious |
Standard Cited |
19100147 D04 I |
Issuance Date |
1995-01-04 |
Abatement Due Date |
1995-01-13 |
Current Penalty |
472.5 |
Initial Penalty |
675.0 |
Nr Instances |
1 |
Nr Exposed |
2 |
Related Event Code (REC) |
Complaint |
Gravity |
01 |
|
|