Filing Number Date Filed Type Effective Date
060816000701 2006-08-16 CERTIFICATE OF INCORPORATION 2006-08-16

OSHA's Inspections within Industry

Inspection Nr Report ID Date Opened Site Address
336242789 0213100 2012-08-29 120 FRONT ST. THE TORCHES ON THE HUDSON, LLC, NEWBURGH, NY, 12550
Inspection Type Other-L
Scope Partial
Safety/Health Safety
Close Conference 2012-08-29
Case Closed 2013-09-03

Related Activity

Type Inspection
Activity Nr 591782
Safety Yes
Type Inspection
Activity Nr 591539
Safety Yes

Violation Items

Citation ID 01001
Citaton Type Serious
Standard Cited 19100303 B01
Issuance Date 2013-01-22
Current Penalty 2800.0
Initial Penalty 2800.0
Final Order 2013-02-15
Nr Instances 1
Nr Exposed 4
Gravity 10
FTA Current Penalty 0.0
Citation text line 29 CFR 1910.303(b)(1): Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees: a) North Dock, 120 Front St. Newburgh, NY on or about 8/20/12, installed dock lighting was not free from recognized hazards in that design and installation of lighting and related components did not comply with applicable provisions of the National Electric Code.
Citation ID 01002
Citaton Type Serious
Standard Cited 19100304 B02 III
Issuance Date 2013-01-22
Current Penalty 2400.0
Initial Penalty 2400.0
Final Order 2013-02-15
Nr Instances 2
Nr Exposed 4
Gravity 5
FTA Current Penalty 0.0
Citation text line 29 CFR 1910.304(b)(2)(iii): The branch circuit wiring method did not include or provide an equipment grounding conductor to which the grounding contacts of the receptacle or cord could be connected: a) North Dock, on or about 8/20/12, No equipment grounding conductor was installed at the galvanized steel light poles exposing employees to shock and burn hazards. b) South dock, 120 Front St Newburgh, On or about 8/21/12, Extension cords were in use from the restaurant outdoor outlet to the dock with no ground pins.
Citation ID 01003
Citaton Type Serious
Standard Cited 19100304 E01 I
Issuance Date 2013-01-22
Current Penalty 2000.0
Initial Penalty 2000.0
Final Order 2013-02-15
Nr Instances 1
Nr Exposed 2
Gravity 5
FTA Current Penalty 0.0
Citation text line 29 CFR 1910.304(e)(1)(i): Conductors and equipment rated 600 volts, nominal, or less were not protected from overcurrent in accordance with their ability to safely conduct current. a) Northern Dock, The Torches on the Hudson, on or about 8/20/2012, the galvanized steel light poles had no over current protection for the circuit exposing employees to shock and burn hazards.
Citation ID 01004
Citaton Type Serious
Standard Cited 19100305 A02 X
Issuance Date 2013-01-22
Abatement Due Date 2013-02-01
Current Penalty 2400.0
Initial Penalty 2400.0
Final Order 2013-02-15
Nr Instances 2
Nr Exposed 4
Gravity 5
FTA Current Penalty 0.0
Citation text line 29 CFR 1910.305(a)(2)(x): Flexible cords and cables were not protected from accidental damage, as might be caused, for example, by sharp corners, projections, and doorways or other pinch points: a) South Dock 120 Front Street Dock On or about 8/21/12, an extension cord was plugged into an outdoor outlet at the restaurant and run underneath a concrete sidewalk, to the dock exposing it to damage. b) North Dock, 120 Front Street Dock On or about 8/21/12, The power cord was worn down to bare copper wire resulting in electrifying the poles exposing employees to shock hazards.
Citation ID 01005
Citaton Type Serious
Standard Cited 19100333 A01
Issuance Date 2013-01-22
Abatement Due Date 2013-01-29
Current Penalty 2800.0
Initial Penalty 2800.0
Final Order 2013-02-15
Nr Instances 1
Nr Exposed 2
Gravity 10
FTA Current Penalty 0.0
Citation text line 29 CFR 1910.333(a)(1): Safety-related work practices were not employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, in that: Live parts to which an employee was exposed were not deenergized before the employee worked on or near them: a) North Dock, The Torches on Hudson, on or about 8/20/2012: Employees were exposed to shock hazards while troubleshooting and repairing dock lighting and did not take adequate precautions to ensure equipment was denergized prior to contact.