Name: | STORM KING PROPERTY MANAGEMENT LTD. |
Jurisdiction: | New York |
Legal type: | DOMESTIC BUSINESS CORPORATION |
Status: | Active |
Date of registration: | 16 Aug 2006 (19 years ago) |
Entity Number: | 3401431 |
ZIP code: | 12553 |
County: | Orange |
Place of Formation: | New York |
Address: | 2899 ROUTE 9W, NEW WINDSOR, NY, United States, 12553 |
Shares Details
Shares issued 200
Share Par Value 0
Type NO PAR VALUE
Name | Role | Address |
---|---|---|
THE CORPORATION | DOS Process Agent | 2899 ROUTE 9W, NEW WINDSOR, NY, United States, 12553 |
Filing Number | Date Filed | Type | Effective Date |
---|---|---|---|
060816000701 | 2006-08-16 | CERTIFICATE OF INCORPORATION | 2006-08-16 |
Inspection Nr | Report ID | Date Opened | Site Address | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
336242789 | 0213100 | 2012-08-29 | 120 FRONT ST. THE TORCHES ON THE HUDSON, LLC, NEWBURGH, NY, 12550 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
Type | Inspection |
Activity Nr | 591782 |
Safety | Yes |
Type | Inspection |
Activity Nr | 591539 |
Safety | Yes |
Violation Items
Citation ID | 01001 |
Citaton Type | Serious |
Standard Cited | 19100303 B01 |
Issuance Date | 2013-01-22 |
Current Penalty | 2800.0 |
Initial Penalty | 2800.0 |
Final Order | 2013-02-15 |
Nr Instances | 1 |
Nr Exposed | 4 |
Gravity | 10 |
FTA Current Penalty | 0.0 |
Citation text line | 29 CFR 1910.303(b)(1): Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees: a) North Dock, 120 Front St. Newburgh, NY on or about 8/20/12, installed dock lighting was not free from recognized hazards in that design and installation of lighting and related components did not comply with applicable provisions of the National Electric Code. |
Citation ID | 01002 |
Citaton Type | Serious |
Standard Cited | 19100304 B02 III |
Issuance Date | 2013-01-22 |
Current Penalty | 2400.0 |
Initial Penalty | 2400.0 |
Final Order | 2013-02-15 |
Nr Instances | 2 |
Nr Exposed | 4 |
Gravity | 5 |
FTA Current Penalty | 0.0 |
Citation text line | 29 CFR 1910.304(b)(2)(iii): The branch circuit wiring method did not include or provide an equipment grounding conductor to which the grounding contacts of the receptacle or cord could be connected: a) North Dock, on or about 8/20/12, No equipment grounding conductor was installed at the galvanized steel light poles exposing employees to shock and burn hazards. b) South dock, 120 Front St Newburgh, On or about 8/21/12, Extension cords were in use from the restaurant outdoor outlet to the dock with no ground pins. |
Citation ID | 01003 |
Citaton Type | Serious |
Standard Cited | 19100304 E01 I |
Issuance Date | 2013-01-22 |
Current Penalty | 2000.0 |
Initial Penalty | 2000.0 |
Final Order | 2013-02-15 |
Nr Instances | 1 |
Nr Exposed | 2 |
Gravity | 5 |
FTA Current Penalty | 0.0 |
Citation text line | 29 CFR 1910.304(e)(1)(i): Conductors and equipment rated 600 volts, nominal, or less were not protected from overcurrent in accordance with their ability to safely conduct current. a) Northern Dock, The Torches on the Hudson, on or about 8/20/2012, the galvanized steel light poles had no over current protection for the circuit exposing employees to shock and burn hazards. |
Citation ID | 01004 |
Citaton Type | Serious |
Standard Cited | 19100305 A02 X |
Issuance Date | 2013-01-22 |
Abatement Due Date | 2013-02-01 |
Current Penalty | 2400.0 |
Initial Penalty | 2400.0 |
Final Order | 2013-02-15 |
Nr Instances | 2 |
Nr Exposed | 4 |
Gravity | 5 |
FTA Current Penalty | 0.0 |
Citation text line | 29 CFR 1910.305(a)(2)(x): Flexible cords and cables were not protected from accidental damage, as might be caused, for example, by sharp corners, projections, and doorways or other pinch points: a) South Dock 120 Front Street Dock On or about 8/21/12, an extension cord was plugged into an outdoor outlet at the restaurant and run underneath a concrete sidewalk, to the dock exposing it to damage. b) North Dock, 120 Front Street Dock On or about 8/21/12, The power cord was worn down to bare copper wire resulting in electrifying the poles exposing employees to shock hazards. |
Citation ID | 01005 |
Citaton Type | Serious |
Standard Cited | 19100333 A01 |
Issuance Date | 2013-01-22 |
Abatement Due Date | 2013-01-29 |
Current Penalty | 2800.0 |
Initial Penalty | 2800.0 |
Final Order | 2013-02-15 |
Nr Instances | 1 |
Nr Exposed | 2 |
Gravity | 10 |
FTA Current Penalty | 0.0 |
Citation text line | 29 CFR 1910.333(a)(1): Safety-related work practices were not employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, in that: Live parts to which an employee was exposed were not deenergized before the employee worked on or near them: a) North Dock, The Torches on Hudson, on or about 8/20/2012: Employees were exposed to shock hazards while troubleshooting and repairing dock lighting and did not take adequate precautions to ensure equipment was denergized prior to contact. |
Date of last update: 28 Mar 2025
Sources: New York Secretary of State