Inspection Type |
Planned
|
Scope |
Complete
|
Safety/Health |
Safety
|
Close Conference |
2014-04-29
|
Emphasis |
L: LOCALTARG, N: CTARGET, P: LOCALTARG
|
Case Closed |
2014-06-26
|
Violation Items
Citation ID |
01001 |
Citaton Type |
Serious |
Standard Cited |
19260102 A01 |
Issuance Date |
2014-05-22 |
Abatement Due Date |
2014-06-02 |
Current Penalty |
900.0 |
Initial Penalty |
1200.0 |
Final Order |
2014-05-22 |
Nr Instances |
1 |
Nr Exposed |
3 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1926.102(a)(1): Eye and face protective equipment were not used when machines or operations presented potential eye or face injury from physical, chemical, or radiation agents. (a) At the jobsite, on or about 4/29/14: Employees performing manual demolition of wood bowling lanes with pry bars, saws, and hammers were not provided with protective eyewear. |
|
Citation ID |
01002A |
Citaton Type |
Serious |
Standard Cited |
19260403 B02 |
Issuance Date |
2014-05-22 |
Abatement Due Date |
2014-06-02 |
Current Penalty |
900.0 |
Initial Penalty |
1200.0 |
Final Order |
2014-05-22 |
Nr Instances |
1 |
Nr Exposed |
3 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification: (a) Jobsite, NW corner of building, on or about 4/29/14: Multiple 4 square boxes with receptacles, connected by lengths of BX cable, were laying on the floor where they were exposed to physical damage from demoliton activities. |
|
Citation ID |
01002B |
Citaton Type |
Serious |
Standard Cited |
19260404 B01 II |
Issuance Date |
2014-05-22 |
Abatement Due Date |
2014-06-02 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2014-05-22 |
Nr Instances |
1 |
Nr Exposed |
3 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1926.404(b)(1)(ii): On a construction site, where an assured equipment grounding program was not utilized, all 120-volt, single-phase, 15 and 20 ampere receptacle outlets which were not a part of the permanent wiring of the building or structure and which are in use by employees did not have approved ground fault circuit interrupers for personal protection. (a) At the jobsite; NW corner of building; on or about 4/29/14: Multiple 4 square boxes with receptacles, connected by lengths of BX cable, were laying on the floor where they were exposed to physical damage from demoliton activities; boxes and wiring were not provided with GFCI protection. |
|
Citation ID |
01002C |
Citaton Type |
Serious |
Standard Cited |
19260405 B02 |
Issuance Date |
2014-05-22 |
Abatement Due Date |
2014-06-02 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2014-05-22 |
Nr Instances |
1 |
Nr Exposed |
3 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1926.405(b)(2): In energized installations, each outlet box did not have a cover, faceplate, or fixture canopy: (a) At the jobsite; temporary panel in center of building, on or about 4/29/14: 120v receptacles were not provided with face plate(s). |
|
Citation ID |
02001 |
Citaton Type |
Other |
Standard Cited |
19260100 A |
Issuance Date |
2014-05-22 |
Abatement Due Date |
2014-06-02 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2014-05-22 |
Nr Instances |
1 |
Nr Exposed |
4 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1926.100(a): Employees were not protected by protective helmets while working in areas where there was a possible danger of head injury from impact, or from falling or flying objects, or from electrical shock and burns: (a) At the jobsite, on or about 4/29/14: Employees performing manual demolition of wood bowling lanes with pry bars, saws, and hammers were not provided with protective helmets for protection from struck-by hazards. (b) At the jobsite, on or about 4/29/14: Employees performing backfilling operations were not provided with protective helmets for protection from struck-by hazards. |
|
Citation ID |
02002 |
Citaton Type |
Other |
Standard Cited |
19260150 C01 VI |
Issuance Date |
2014-05-22 |
Abatement Due Date |
2014-06-02 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2014-05-22 |
Nr Instances |
1 |
Nr Exposed |
3 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1926.150(c)(1)(vi): A fire extinguisher, rated not less than 10B, shall be provided within 50 feet of wherever more than 5 gallons of flammable or combustible liquids or 5 pounds of flammable gas are being used on the jobsite. This requirement does not apply to the integral fuel tanks of motor vehicles. (a) At the jobsite, NW and SW ends of buildings near exits, on or about 4/29/14: Mulitple safety cans containing 2.5 to 5 gallons of gasoline were stored inside the building; no fire extinguishers were provided. |
|
|