Citation ID |
01001 |
Citaton Type |
Serious |
Standard Cited |
19100024 H |
Issuance Date |
2013-02-04 |
Abatement Due Date |
2013-03-01 |
Current Penalty |
1000.0 |
Initial Penalty |
2000.0 |
Final Order |
2013-02-27 |
Nr Instances |
1 |
Nr Exposed |
2 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.24(h): Standard railings were not provided on the open sides of all exposed stairways and stair platforms: a) On or about 12/11/2012 in the assembly area - where there was no railing on the open side of the stairway to the upstairs assembly area. ABATEMENT CERTIFICATION REQUIRED |
|
Citation ID |
01002 |
Citaton Type |
Serious |
Standard Cited |
19100036 D01 |
Issuance Date |
2013-02-04 |
Abatement Due Date |
2013-03-01 |
Current Penalty |
1000.0 |
Initial Penalty |
2000.0 |
Final Order |
2013-02-27 |
Nr Instances |
1 |
Nr Exposed |
5 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.36(d)(1): A required exit(s), way of approach thereto, and/or way of travel from the exit into the street or open space, was not continuously maintained free of all obstructions or impediments to full instant use in the case of fire or other emergency: a) On or about 12/11/2012 in the metal fabrication room; where the exit door was locked in the closed position with three sliding bolt locks (top, middle and bottom). ABATEMENT CERTIFICATION REQUIRED |
|
Citation ID |
01003 |
Citaton Type |
Serious |
Standard Cited |
19100106 E02 IV A |
Issuance Date |
2013-02-04 |
Abatement Due Date |
2013-03-01 |
Current Penalty |
1000.0 |
Initial Penalty |
2000.0 |
Final Order |
2013-02-27 |
Nr Instances |
1 |
Nr Exposed |
2 |
Related Event Code (REC) |
Complaint |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.106(e)(2)(iv)(a): Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 F (37.8 C), were not kept in covered containers when not actually in use: a) On or about 12/11/2012 in the paint room - where there was an open, uncovered 5 gallon pail of solvent. ABATEMENT CERTIFICATION REQUIRED |
|
Citation ID |
01004 |
Citaton Type |
Other |
Standard Cited |
19100107 C06 |
Issuance Date |
2013-02-04 |
Abatement Due Date |
2013-03-01 |
Current Penalty |
0.0 |
Initial Penalty |
2800.0 |
Final Order |
2013-02-27 |
Nr Instances |
1 |
Nr Exposed |
2 |
Related Event Code (REC) |
Complaint |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.107(c)(6): Electrical wiring and equipment not subject to deposits of combustible residues but located in a spraying area as herein defined were not explosion-proof type approved for Class I, group D locations and did not otherwise conform to the provisions of subpart S of this part, for Class I, Division 1, Hazardous Locations: a) On or about 12/11/2012 in the paint room - where standard duty electrical equipment including, but not limited to: switches, lighting and motors, was installed in the area where spray finishing of flammable coatings was performed. ABATEMENT DOCUMENTATION REQUIRED |
|
Citation ID |
01005 |
Citaton Type |
Serious |
Standard Cited |
19100212 A03 II |
Issuance Date |
2013-02-04 |
Abatement Due Date |
2013-03-01 |
Current Penalty |
1000.0 |
Initial Penalty |
2000.0 |
Final Order |
2013-02-27 |
Nr Instances |
1 |
Nr Exposed |
2 |
Related Event Code (REC) |
Complaint |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.212(a)(3)(ii): Point(s) of operation of machinery were not guarded to prevent employee(s) from having any part of their body in the danger zone(s) during operating cycle(s): a) On or about 12/11/2012 in the fabrication area - where the table saw used for cutting metal and plastic was not provided with a guard for the saw blade. ABATEMENT CERTIFICATION REQUIRED |
|
Citation ID |
01006 |
Citaton Type |
Serious |
Standard Cited |
19100303 B02 |
Issuance Date |
2013-02-04 |
Abatement Due Date |
2013-03-01 |
Current Penalty |
1000.0 |
Initial Penalty |
2000.0 |
Final Order |
2013-02-27 |
Nr Instances |
1 |
Nr Exposed |
2 |
Related Event Code (REC) |
Complaint |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) On or about 12/11/2012 in the metal fabrication room - where a metal duplex receptacle box at the end of a flexible cord was used as an extension cord. The metal box was not securely mounted as required by the National Electrical Code. ABATEMENT CERTIFICATION REQUIRED |
|
Citation ID |
01007 |
Citaton Type |
Serious |
Standard Cited |
19100303 G02 I |
Issuance Date |
2013-02-04 |
Abatement Due Date |
2013-03-01 |
Current Penalty |
1000.0 |
Initial Penalty |
2000.0 |
Final Order |
2013-02-27 |
Nr Instances |
1 |
Nr Exposed |
3 |
Related Event Code (REC) |
Complaint |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): a) On or about 12/11/2012 in the router operations room - where the electrical panel for the heater and receptacles was missing the front cover, exposing employees to "live" electrical parts. ABATEMENT CERTIFICATION REQUIRED |
|