344437520
|
0215000
|
2019-10-24
|
713 53RD ST., BROOKLYN, NY, 11220
|
|
Inspection Type |
FollowUp
|
Scope |
Complete
|
Safety/Health |
Safety
|
Close Conference |
2019-10-24
|
Case Closed |
2020-01-17
|
Related Activity
Type |
Inspection |
Activity Nr |
1385375 |
Safety |
Yes |
|
|
344437397
|
0215000
|
2019-10-24
|
840 51ST ST., BROOKLYN, NY, 11220
|
|
Inspection Type |
FollowUp
|
Scope |
Partial
|
Safety/Health |
Safety
|
Close Conference |
2019-10-24
|
Case Closed |
2020-01-17
|
Related Activity
Type |
Inspection |
Activity Nr |
1393030 |
Safety |
Yes |
|
|
344398326
|
0215000
|
2019-10-23
|
550 51ST, BROOKLYN, NY, 11220
|
|
Inspection Type |
FollowUp
|
Scope |
Partial
|
Safety/Health |
Safety
|
Close Conference |
2019-10-23
|
Emphasis |
L: LOCALTARG
|
Case Closed |
2020-01-13
|
Related Activity
Type |
Inspection |
Activity Nr |
1386691 |
Safety |
Yes |
|
|
343930350
|
0215000
|
2019-04-09
|
853 59TH ST., BROOKLYN, NY, 11220
|
|
Inspection Type |
Planned
|
Scope |
Complete
|
Safety/Health |
Safety
|
Close Conference |
2019-04-09
|
Emphasis |
L: LOCALTARG, P: LOCALTARG
|
Violation Items
Citation ID |
01001 |
Citaton Type |
Serious |
Standard Cited |
19260405 J01 II |
Issuance Date |
2019-08-13 |
Current Penalty |
6630.0 |
Initial Penalty |
6630.0 |
Final Order |
2019-09-09 |
Nr Instances |
1 |
Nr Exposed |
4 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1926.405(j)(1)(ii): Fixtures, lampholders, rosettes, or receptacles were not securely supported. a) 3rd and 4th floor: Energized electrical receptacles and light switches were not securely supported. They were left hanging by energized wires attached to the devices. On or about 04/09/19. |
|
|
343923538
|
0215000
|
2019-04-09
|
748 58TH STREET, BROOKLYN, NY, 11220
|
|
Inspection Type |
Planned
|
Scope |
Partial
|
Safety/Health |
Safety
|
Close Conference |
2019-04-09
|
Emphasis |
L: LOCALTARG, P: LOCALTARG
|
Violation Items
Citation ID |
01001 |
Citaton Type |
Serious |
Standard Cited |
19260403 B02 |
Issuance Date |
2019-08-13 |
Current Penalty |
6630.0 |
Initial Penalty |
6630.0 |
Final Order |
2019-09-10 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification. Location: a) On first floor of the jobsite: On or about 04/09/19, employee used a power tap to energize electrical equipment. The power tap was not listed to be use in a construction work environment. |
|
|
343930301
|
0215000
|
2019-04-09
|
840 51ST ST., BROOKLYN, NY, 11220
|
|
Inspection Type |
Planned
|
Scope |
Complete
|
Safety/Health |
Safety
|
Close Conference |
2019-04-09
|
Emphasis |
P: LOCALTARG, L: LOCALTARG
|
Case Closed |
2020-01-23
|
Violation Items
Citation ID |
01001 |
Citaton Type |
Serious |
Standard Cited |
19260020 B02 |
Issuance Date |
2019-08-13 |
Abatement Due Date |
2019-08-23 |
Current Penalty |
6630.0 |
Initial Penalty |
6630.0 |
Final Order |
2019-09-10 |
Nr Instances |
1 |
Nr Exposed |
2 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1926.20(b)(2): The employer did not initiate and maintain a safety program which provides for frequent and regular inspections of jobsites, materials, and equipment to be made by a competent person (i.e., a person who is capable of identifying existing hazards.) a) Jobsite: The employer did not initiate and maintain a safety program which provides for frequent and regular inspections of jobsites, materials, and equipment to be made by a competent person. Employees were exposed to hazards, including but not limited to: did not have free and unobstructed egress in case of emergency, used extension cords with missing ground pins, used electric powered hand tools and extension cords without GFCI protection, and used energized electrical receptacles and light switches that were not securely supported. On or about 04/09/19. |
|
Citation ID |
01002 |
Citaton Type |
Serious |
Standard Cited |
19260034 A |
Issuance Date |
2019-08-13 |
Current Penalty |
9282.0 |
Initial Penalty |
9282.0 |
Final Order |
2019-09-10 |
Nr Instances |
1 |
Nr Exposed |
2 |
Gravity |
10 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1926.34(a): A lock or fastening to prevent free escape from the inside of any building was installed. Building or structure exits were not so arranged and maintained as to provide free and unobstructed egress from all parts of the building or structure at all times when it was occupied. a) Jobsite entrance, 1st floor: The entrance and exit door to worksite was locked. Employees were working in the building did not have free and unobstructed egress. On or about 04/09/19. |
|
Citation ID |
01003 |
Citaton Type |
Serious |
Standard Cited |
19260404 B01 I |
Issuance Date |
2019-08-13 |
Abatement Due Date |
2019-08-21 |
Current Penalty |
6630.0 |
Initial Penalty |
6630.0 |
Final Order |
2019-09-10 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1926.404(b)(1)(i): Employer did not use either ground fault circuit interrupters as specified in paragraph (b)(1)(ii) of this section, or an assured equipment grounding conductor program as specified in paragraph (b)(1)(iii) of this section to protect employees on construction sites. a) Backyard, stairwell to the 1st floor: An employee used an electric powered rotary hammer to break concrete and bricks for stairwell installation work. The rotary hammer was connected to an extension cord, which was not provided with a ground fault circuit interrupter. On or about 04/09/19. |
|
Citation ID |
01004 |
Citaton Type |
Serious |
Standard Cited |
19260404 F06 |
Issuance Date |
2019-08-13 |
Abatement Due Date |
2019-08-21 |
Current Penalty |
6630.0 |
Initial Penalty |
6630.0 |
Final Order |
2019-09-10 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1926.404(f)(6): The path to ground from circuits, equipment, or enclosures was not permanent and continuous. a) Backyard, stairwell to the 1st floor: An employee used an electric powered rotary hammer to break concrete and bricks for stairwell installation work. The rotary hammer was connected to an extension cord, which was missing a ground pin. On or about 04/09/19. |
|
Citation ID |
01005 |
Citaton Type |
Serious |
Standard Cited |
19260405 J01 II |
Issuance Date |
2019-08-13 |
Abatement Due Date |
2019-08-21 |
Current Penalty |
5304.0 |
Initial Penalty |
5304.0 |
Final Order |
2019-09-10 |
Nr Instances |
1 |
Nr Exposed |
2 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1926.405(j)(1)(ii): Fixtures, lampholders, rosettes, or receptacles were not securely supported. a) 1st floor and basement: Energized electrical receptacles and light switches were not securely supported. They were left hanging by energized wires attached to the devices. On or about 04/09/19. |
|
|
343866919
|
0215000
|
2019-03-20
|
550 51ST, BROOKLYN, NY, 11220
|
|
Inspection Type |
Planned
|
Scope |
Partial
|
Safety/Health |
Safety
|
Close Conference |
2019-03-20
|
Emphasis |
P: LOCALTARG, L: LOCALTARG
|
Violation Items
Citation ID |
01001 |
Citaton Type |
Serious |
Standard Cited |
19260405 A02 II E |
Issuance Date |
2019-08-13 |
Abatement Due Date |
2019-08-21 |
Current Penalty |
5304.0 |
Initial Penalty |
5304.0 |
Final Order |
2019-09-10 |
Nr Instances |
3 |
Nr Exposed |
7 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1926.405(a)(2)(ii)(E): Lamps used in temporary wiring for general illumination were not protected from accidental contact or breakage: Location:550 51st On or about 03/20/19 a) Employees were entering and exiting the worksite were temporary lighting was not protected from breakage. |
|
|
343853750
|
0215000
|
2019-03-12
|
713 53RD STREET, BROOKLYN, NY, 11220
|
|
Inspection Type |
Planned
|
Scope |
Complete
|
Safety/Health |
Safety
|
Close Conference |
2019-03-12
|
Emphasis |
P: LOCALTARG, L: LOCALTARG
|
Case Closed |
2023-01-11
|
Violation Items
Citation ID |
01001 |
Citaton Type |
Serious |
Standard Cited |
19260403 I02 I |
Issuance Date |
2019-08-13 |
Abatement Due Date |
2019-08-21 |
Current Penalty |
9282.0 |
Initial Penalty |
9282.0 |
Final Order |
2019-09-10 |
Nr Instances |
1 |
Nr Exposed |
4 |
Gravity |
10 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1926.403(i)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by cabinets or other forms of enclosures, nor by any of the means listed in subparagraphs (A) through (D) of this paragraph. Location: 713 53rd Street Brooklyn NY On or about: March 12, 2019 a) An electrical breaker panel on the 2nd floor was not provided with a cover. |
|
Citation ID |
01002 |
Citaton Type |
Serious |
Standard Cited |
19260405 J01 I |
Issuance Date |
2019-08-13 |
Abatement Due Date |
2019-08-21 |
Current Penalty |
5304.0 |
Initial Penalty |
5304.0 |
Final Order |
2019-09-10 |
Nr Instances |
2 |
Nr Exposed |
2 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1926.405(j)(1)(i): Fixtures, lampholders, lamps, rosettes, or receptacles had live parts normally exposed to employee contact: Location: 713 53rd Street Brooklyn NY On or about: March 12, 2019 a) Power tools, temporary lights and other equipment was energized by a electrical receptacle which had live parts exposed. |
|
Citation ID |
01003 |
Citaton Type |
Serious |
Standard Cited |
19261052 B01 |
Issuance Date |
2019-08-13 |
Abatement Due Date |
2019-08-21 |
Current Penalty |
5304.0 |
Initial Penalty |
5304.0 |
Final Order |
2019-09-10 |
Nr Instances |
1 |
Nr Exposed |
8 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1926.1052(b)(1): Foot traffic was not prohibited on stairways where the treads and/or landings of pan stairs were to be filled in with concrete or other material at a later date and stairs were not temporarily fitted with wood or other solid material at least to the top edge of each pan. Location: 713 53rd Street Brooklyn NY On or about: March 12, 2019 a) Employees used stairway which were not temporarily filled or fitted with wood or other materials. Stairway used to access the work area on the roof. |
|
|