Citation ID |
01001A |
Citaton Type |
Serious |
Standard Cited |
19100106 E06 I |
Issuance Date |
2018-02-14 |
Current Penalty |
1330.2 |
Initial Penalty |
2217.0 |
Final Order |
2018-03-09 |
Nr Instances |
1 |
Nr Exposed |
10 |
Related Event Code (REC) |
Referral |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.106(e)(6)(i): Adequate precautions against the ignition of flammable vapors were not taken: a) Production Floor, on or about 9/15/17: Employees dispense the following flammable materials including but not limited to: Resin Polyester C1-3001-23; Acetone and Hetron FR 650 T-20 Resin without grounding the containers. |
|
Citation ID |
01001B |
Citaton Type |
Serious |
Standard Cited |
19100106 E06 II |
Issuance Date |
2018-02-14 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2018-03-09 |
Nr Instances |
1 |
Nr Exposed |
10 |
Related Event Code (REC) |
Referral |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.106(e)(6)(ii): Class I flammable liquid(s) were dispensed into containers without electrically interconnecting the nozzle and the container: a) Production Floor, on or about 9/15/17: Employees dispense the following flammable materials from a 55 gallon drum to a secondary container with no means of electrically interconnecting the nozzle and the portable container. Flammable materials include but not limited to: Resin Polyester C1-3001-23; Acetone; Hetron FR 650 T-20 Resin and Flammable Waste. |
|
Citation ID |
01002A |
Citaton Type |
Serious |
Standard Cited |
19100106 E02 II B 2 |
Issuance Date |
2018-02-14 |
Current Penalty |
1330.2 |
Initial Penalty |
2217.0 |
Final Order |
2018-03-09 |
Nr Instances |
2 |
Nr Exposed |
10 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.106(e)(2)(ii)(b)(2): More than 120 gallons of Category 2, 3, or 4 flammable or combustible liquids in containers were located outside of inside storage room(s) or storage cabinet(s): a) Production Floor, on or about 9/15/17: Storage of Category 2 and 3 flammable materials exceeded 120 gallons, flammable material was approximately 325 gallons located outside if an inside storage room. b) Trimming Department, on or about 9/15/17: Storage of Category 2 and 3 flammable materials exceeded 120 gallons, flammable material was approximately 385 gallons located outside if an inside storage room. |
|
Citation ID |
01002B |
Citaton Type |
Serious |
Standard Cited |
19100106 E02 IV D |
Issuance Date |
2018-02-14 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2018-03-09 |
Nr Instances |
1 |
Nr Exposed |
10 |
Related Event Code (REC) |
Referral |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.106(e)(2)(iv)(d): Flammable or combustible liquids were not drawn from or transferred into vessel(s), container(s), or portable tank(s) within a building through a closed piping system, from safety cans, by means of a device drawing through the top, or from a container or portable tank by gravity through an approved self closing valve: a) Production Floor, on or about 9/15/17: Polyester Resin C1 3001-23 a flammable liquid was being dispensed through a non self closing valve. |
|
Citation ID |
01003 |
Citaton Type |
Serious |
Standard Cited |
19100107 G02 |
Issuance Date |
2018-02-14 |
Abatement Due Date |
2018-04-12 |
Current Penalty |
1330.2 |
Initial Penalty |
2217.0 |
Final Order |
2018-03-09 |
Nr Instances |
1 |
Nr Exposed |
10 |
Related Event Code (REC) |
Referral |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.107(g)(2): Spraying area(s) were not kept free from the accumulation of deposits of combustible residues: a) Production Floor, on or about 9/15/17: There was an accumulation of combustible residues on the mold carts, flammable materials used when manufacturing header molds. |
|
Citation ID |
01004A |
Citaton Type |
Serious |
Standard Cited |
19100134 C01 |
Issuance Date |
2018-02-14 |
Abatement Due Date |
2018-04-12 |
Current Penalty |
997.8 |
Initial Penalty |
1663.0 |
Final Order |
2018-03-09 |
Nr Instances |
1 |
Nr Exposed |
3 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.134(c)(1): Employer did not establish nor implement a written respiratory protection program with worksite specific procedures when respirators were necessary to protect the health of the employee or whenever respirators were required by the employer: a) Production Floor and Trimming Department, on or about 9/15/17: Employer had not established a written respirator protection program when employees were required to wear full face air purifying respirators. |
|
Citation ID |
01004B |
Citaton Type |
Serious |
Standard Cited |
19100134 F02 |
Issuance Date |
2018-02-14 |
Abatement Due Date |
2018-04-12 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2018-03-09 |
Nr Instances |
1 |
Nr Exposed |
3 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.134(f)(2): Employer did not ensure that an employee using a tight fitting face piece respirator was fit tested prior to initial use of the respirator, whenever a different respirator face piece (size, style, model or make) was used, and at least annually thereafter: a) Production Floor and Trimming Department, on or about 9/15/17: Employees required to wear full face air purifying respirators had not been fit tested. |
|
Citation ID |
01004C |
Citaton Type |
Serious |
Standard Cited |
19100134 K |
Issuance Date |
2018-02-14 |
Abatement Due Date |
2018-04-12 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2018-03-09 |
Nr Instances |
1 |
Nr Exposed |
3 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.134(k) The employer did not provide effective, comprehensive, understandable, and annual (or more often if necessary) training to employees who are required to use respirators: a) Production Floor and Trimming Department, on or about 9/15/17: Employees are required to wear full face air purifying respirators and had not received respirator training. |
|
Citation ID |
01005 |
Citaton Type |
Serious |
Standard Cited |
19100178 L01 |
Issuance Date |
2018-02-14 |
Abatement Due Date |
2018-04-12 |
Current Penalty |
1330.2 |
Initial Penalty |
2217.0 |
Final Order |
2018-03-09 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.178(l)(1)(i): The employer did not ensure that each powered industrial truck operator was competent to operate a powered industrial truck safely, demonstrated by the successful completion of the training and evaluation specified in this paragraph (l): a) Production Floor, on or about 9/15/17: Powered industrial truck operator was not provided with training. |
|
Citation ID |
01006 |
Citaton Type |
Serious |
Standard Cited |
19101200 E01 |
Issuance Date |
2018-02-14 |
Abatement Due Date |
2018-04-12 |
Current Penalty |
997.8 |
Initial Penalty |
1663.0 |
Final Order |
2018-03-09 |
Nr Instances |
1 |
Nr Exposed |
10 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.1200(e)(1): The employer did not develop, implement, and/or maintain at the workplace a written hazard communication program which describes how the criteria specified in 29 CFR 1910.1200(f), (g), and (h) will be met: 1) Labeling and other forms of warning; 2) SDS requirements for the hazardous materials known to be present at the jobsite; 3) Employee training and information. The written program must also include: (a) A list of all the chemicals used at the jobsite. (b) Methods to inform employees of hazards associated with non-routine tasks. (c) Methods the employer will use to inform any contractors employees of workplace hazards. a) Production Floor, on or about 9/15/17: A written hazard communication program was not developed for the employees who work with hazardous materials including but not limited to: Ford Glacier White Ultra Plus; Polyester Resin C1 3001-23; Hetron FR 650 T-20 Resin Luperox DDM-9 Organic Peroxide and Acetone. |
|