Citation ID |
01001A |
Citaton Type |
Serious |
Standard Cited |
19100146 E06 |
Issuance Date |
2015-05-01 |
Abatement Due Date |
2015-06-05 |
Current Penalty |
3750.0 |
Initial Penalty |
5000.0 |
Final Order |
2015-05-12 |
Nr Instances |
1 |
Nr Exposed |
3 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.146(e)(6): The employer did not retain each canceled entry permit for at least one year to facilitate the review of the permit-required confined space program required by 29 CFR 1910.146(d)(14): a) At the facility, on or about 3/4/15: The employer did not retain each entry permit from the past year. A permit was not available for an entry into the Carter Daye dust collector performed in August 2014. Abatement certification must be submitted for this item. |
|
Citation ID |
01001B |
Citaton Type |
Serious |
Standard Cited |
19100146 F07 |
Issuance Date |
2015-05-01 |
Abatement Due Date |
2015-06-05 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2015-05-12 |
Nr Instances |
1 |
Nr Exposed |
3 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.146(f)(7): The entry permit that documented compliance and authorized entry to a permit space did not identify the hazards of the permit space to be entered: a) In the Carter Daye dust collector, on or about 2/18/15: The hazard of airborne combustible dust generated from bag cleaning inside the dust collector was not documented on entry permits. Abatement certification must be submitted for this item. |
|
Citation ID |
01001C |
Citaton Type |
Serious |
Standard Cited |
19100146 F08 |
Issuance Date |
2015-05-01 |
Abatement Due Date |
2015-06-05 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2015-05-12 |
Nr Instances |
1 |
Nr Exposed |
3 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.146(f)(8): The entry permit that documented compliance and authorized entry to a permit space did not identify the measures used to isolate the permit space and to eliminate or control permit space hazards before entry: a) In the Carter Daye dust collector, on or about 2/18/15: The confined space entry permit did not identify the use of lockout tagout for the rotary valve located at the bottom of the dust collector. Abatement certification must be submitted for this item. |
|
Citation ID |
01001D |
Citaton Type |
Serious |
Standard Cited |
19100146 K01 I |
Issuance Date |
2015-05-01 |
Abatement Due Date |
2015-06-05 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2015-05-12 |
Nr Instances |
1 |
Nr Exposed |
3 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.146(k)(1)(i): An employer who designated rescue and emergency services, pursuant to paragraph (d)(9) of this section, did not evaluate a prospective rescuer's ability to respond to a rescue summons in a timely manner, considering the hazard(s) identified: a) At the facility, on or about 3/4/15: The permit required confined space program designated rescue and emergency services to the fire department/emergency services. The employer had not communicated to these outside sources that they had designated them for rescue and emergency services, and had not evaluated their ability to respond. Abatement certification must be submitted for this item. |
|
Citation ID |
01001E |
Citaton Type |
Serious |
Standard Cited |
19100146 K01 II |
Issuance Date |
2015-05-01 |
Abatement Due Date |
2015-06-05 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2015-05-12 |
Nr Instances |
1 |
Nr Exposed |
3 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.146(k)(1)(ii): When designating rescue and emergency services pursuant to paragraph (d)(9), the employer did not evaluate the prospective rescuer's ability, in terms of proficiency with rescue-related tasks and equipment, to function appropriately while rescuing entrants from the particular space or types of spaces identified: a) At the facility, on or about 3/4/15: The permit required confined space program designated rescue and emergency services to the fire department/emergency services. The employer had not communicated to these outside sources that they had designated them for rescue and emergency services, and had not evaluated their ability to respond. Abatement certification must be submitted for this item. |
|
Citation ID |
02001 |
Citaton Type |
Other |
Standard Cited |
19100147 C06 II |
Issuance Date |
2015-05-01 |
Abatement Due Date |
2015-06-05 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2015-05-12 |
Nr Instances |
1 |
Nr Exposed |
2 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.147(c)(6)(ii): The employer did not certify that periodic inspections of the energy control procedures had been performed: a) At the facility, on or about 3/4/15: The employer did not certify that periodic inspections of energy control procedures had been performed for equipment including but not limited to sandblaster, cupper, and pad printer. Abatement certification must be submitted for this item. |
|
Citation ID |
02002 |
Citaton Type |
Other |
Standard Cited |
19100151 C |
Issuance Date |
2015-05-01 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2015-05-12 |
Nr Instances |
1 |
Nr Exposed |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use: a) Next to the boiler, on or about 2/18/15: Where employees added corrosive boiler treatment chemicals, the eye wash station provided did not provide at least 15 minutes of flow. |
|