Inspection Nr | Report ID | Date Opened | Site Address | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
344123310 | 0215000 | 2019-07-01 | 2036 64TH STREET, BROOKLYN, NY, 11204 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
Citation ID | 01001 |
Citaton Type | Serious |
Standard Cited | 19260403 B02 |
Issuance Date | 2019-12-16 |
Current Penalty | 1750.0 |
Initial Penalty | 2273.0 |
Final Order | 2020-03-27 |
Nr Instances | 2 |
Nr Exposed | 2 |
Gravity | 5 |
FTA Current Penalty | 0.0 |
Citation text line | 29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification. Location: 2036 64th Street, Brooklyn, NY. On or about 7/1/2019 a) A portable power strip not rated for use on a construction site was used to energized tools and equipment.. |
Citation ID | 01002 |
Citaton Type | Serious |
Standard Cited | 19260403 I02 I |
Issuance Date | 2019-12-16 |
Current Penalty | 1750.0 |
Initial Penalty | 2842.0 |
Final Order | 2020-03-27 |
Nr Instances | 1 |
Nr Exposed | 2 |
Gravity | 5 |
FTA Current Penalty | 0.0 |
Citation text line | 29 CFR 1926.403(i)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by cabinets or other forms of enclosures, nor by any of the means listed in subparagraphs (A) through (D) of this paragraph. Location: 2036 64th Street, Brooklyn, NY. On or about 7/1/2019 a) An energized electric meter box was not installed with an electric meter. The live parts were covered with a piece of corrugated cardboard. |
Citation ID | 01003A |
Citaton Type | Serious |
Standard Cited | 19260405 G02 IV |
Issuance Date | 2019-12-16 |
Current Penalty | 2000.0 |
Initial Penalty | 2273.0 |
Final Order | 2020-03-27 |
Nr Instances | 2 |
Nr Exposed | 2 |
Gravity | 5 |
FTA Current Penalty | 0.0 |
Citation text line | 29 CFR 1926.405(g)(2)(iv): Flexible cords were not connected to devices and fittings so that strain relief is provided to prevent pull from being directly transmitted to joints or terminal screws. Location: 2036 64th Street, Brooklyn, NY. On or about 7/1/2019 a) A black flexible cord connected to the electrical breaker panel was not installed with any strain relief device. b) A black flexible cord connected to a 4x4 metallic electrical outlet box was not installed with any strain relief device. |
Citation ID | 01003B |
Citaton Type | Serious |
Standard Cited | 19260405 G02 V |
Issuance Date | 2019-12-16 |
Current Penalty | 0.0 |
Initial Penalty | 0.0 |
Final Order | 2020-03-27 |
Nr Instances | 2 |
Nr Exposed | 2 |
Gravity | 5 |
FTA Current Penalty | 0.0 |
Citation text line | 29 CFR 1926.405(g)(2)(v): Flexible cords and cables were not protected by bushings or fittings where passing through holes in covers, outlet boxes, or similar enclosures. Location: 2036 64th Street, Brooklyn, NY. On or about 7/1/2019 a) A black flexible cord wired through and entered the electrical breaker panel was not installed with any bushing or fitting to protect the cord from frayed. b) A black flexible cord wired through a hole of a 4x4 metallic electrical outlet box was not installed with any bushing or fitting to protect the cord from frayed. |