Search icon

E&S ELECTRICAL CORP.

Company Details

Name: E&S ELECTRICAL CORP.
Jurisdiction: New York
Legal type: DOMESTIC BUSINESS CORPORATION
Status: Active
Date of registration: 05 Mar 2018 (7 years ago)
Entity Number: 5297142
ZIP code: 11103
County: Queens
Place of Formation: New York
Address: 2425 STEINWAY ST APT 14, LONG IS CITY, NY, United States, 11103

Shares Details

Shares issued 200

Share Par Value 0

Type NO PAR VALUE

DOS Process Agent

Name Role Address
E&S ELECTRICAL CORP DOS Process Agent 2425 STEINWAY ST APT 14, LONG IS CITY, NY, United States, 11103

Chief Executive Officer

Name Role Address
ERALD SULEJMANI Chief Executive Officer 2425 STEINWAY ST APT 14, LONG IS CITY, NY, United States, 11103

History

Start date End date Type Value
2024-05-30 2024-05-30 Address 2425 STEINWAY ST APT 14, LONG IS CITY, NY, 11103, USA (Type of address: Chief Executive Officer)
2024-05-30 2024-12-05 Shares Share type: NO PAR VALUE, Number of shares: 200, Par value: 0
2024-05-30 2024-05-30 Address 5996 GRAND AVE, MASPETH, NY, 11378, USA (Type of address: Chief Executive Officer)
2023-04-19 2024-05-30 Address 5996 GRAND AVE, MASPETH, NY, 11378, USA (Type of address: Chief Executive Officer)
2023-04-19 2024-05-30 Shares Share type: NO PAR VALUE, Number of shares: 200, Par value: 0
2023-04-19 2024-05-30 Address 2425 STEINWAY ST APT 14, ASTORIA, NY, 11103, USA (Type of address: Service of Process)
2018-03-05 2023-04-19 Address 2425 STEINWAY ST APT 14, ASTORIA, NY, 11103, USA (Type of address: Service of Process)
2018-03-05 2023-04-19 Shares Share type: NO PAR VALUE, Number of shares: 200, Par value: 0

Filings

Filing Number Date Filed Type Effective Date
240530018637 2024-05-30 BIENNIAL STATEMENT 2024-05-30
230419003390 2023-04-19 BIENNIAL STATEMENT 2022-03-01
180305010170 2018-03-05 CERTIFICATE OF INCORPORATION 2018-03-05

OSHA's Inspections within Industry

Inspection Nr Report ID Date Opened Site Address
347472532 0215000 2024-05-09 132 W 14TH STREET, NEW YORK, NY, 10011
Inspection Type Complaint
Scope Partial
Safety/Health Safety
Close Conference 2024-05-09

Related Activity

Type Inspection
Activity Nr 1747322
Safety Yes
Type Complaint
Activity Nr 2160437
Safety Yes
Type Inspection
Activity Nr 1747317
Safety Yes

Violation Items

Citation ID 01001
Citaton Type Serious
Standard Cited 19260405 G02 V
Issuance Date 2024-10-11
Current Penalty 4839.0
Initial Penalty 4839.0
Contest Date 2024-11-06
Nr Instances 1
Nr Exposed 2
Related Event Code (REC) Complaint
Gravity 10
FTA Current Penalty 0.0
Citation text line 29 CFR 1926.405(g)(2)(v): Flexible cords and cables were not protected by bushings or fittings where passing through holes in covers, outlet boxes, or similar enclosures: Location: a) Cellar of the building, 132 West 14th Street, New York, NY 10011 On or about April 24th, 2024, employees were exposed to electrical hazards. The incoming feeding cable entered the breaker panel was not protected from abrasion by using a busing or fitting at the entrance.
Citation ID 01002
Citaton Type Serious
Standard Cited 19260416 A01
Issuance Date 2024-10-11
Current Penalty 4839.0
Initial Penalty 4839.0
Contest Date 2024-11-06
Nr Instances 1
Nr Exposed 2
Related Event Code (REC) Complaint
Gravity 10
FTA Current Penalty 0.0
Citation text line 29 CFR 1926.416(a)(1): The employer permitted employees to work in close proximity to energized, unguarded, and ungrounded electric power circuits that the employee could contact in the course of their work: Location: a) Cellar of the building, 132 West 14th Street, New York, NY 10011 On or about April 24th, 2024, two employees were running 2BX cables from the elevator shelf on the 8th floor to the cellar to be connected to the energized 3-phase 480-V electrical panel. Employees were not protected against electric shock by de-energizing the panels or wearing personal protective equipment with insulation.
Citation ID 02001
Citaton Type Other
Standard Cited 19040039 A02
Issuance Date 2024-10-11
Current Penalty 3457.0
Initial Penalty 3457.0
Contest Date 2024-11-06
Nr Instances 1
Nr Exposed 1
Related Event Code (REC) Complaint
FTA Current Penalty 0.0
Citation text line 29 CFR 1904.39(a)(2): The employer did not report within 24-hours a work-related incident resulting in in-patient hospitalization, amputation or the loss of an eye. Location: a) Cellar of the building, 132 West 14th Street, New York, NY 10011 On or about April 24th, 2024, the employer did not report within 24 hours a work-related incident in which an employee suffered from electrical shocks and burns and was hospitalized for injuries. The incident occurred on 04/24/2024, and OSHA was notified on 05/08/2024.

Date of last update: 24 Mar 2025

Sources: New York Secretary of State