Inspection Nr | Report ID | Date Opened | Site Address | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
340202084 | 0215000 | 2015-01-23 | 96 WYTHE AVE, BROOKLYN, NY, 11249 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
Type | Inspection |
Activity Nr | 1020190 |
Safety | Yes |
Type | Inspection |
Activity Nr | 1020167 |
Safety | Yes |
Type | Inspection |
Activity Nr | 1020197 |
Safety | Yes |
Violation Items
Citation ID | 01001 |
Citaton Type | Serious |
Standard Cited | 19260404 B01 I |
Issuance Date | 2015-04-16 |
Current Penalty | 1400.0 |
Initial Penalty | 2000.0 |
Final Order | 2015-05-22 |
Nr Instances | 1 |
Nr Exposed | 1 |
Gravity | 5 |
FTA Current Penalty | 0.0 |
Citation text line | 29 CFR 1926.404(b)(1)(i): Employer did not use either ground fault circuit interrupters as specified in paragraph (b)(1)(ii) of this section, or an assured equipment grounding conductor program as specified in paragraph (b)(1)(iii) of this section to protect employees on construction sites. a) Parking Garage near front of the building: On or about January 23, 2015 The temporary outlet box mounted to the concrete column was used to provide power and GFCI protection was not provided when using portable tools. |
Citation ID | 01002 |
Citaton Type | Serious |
Standard Cited | 19260404 F06 |
Issuance Date | 2015-04-16 |
Current Penalty | 1400.0 |
Initial Penalty | 2000.0 |
Final Order | 2015-05-22 |
Nr Instances | 1 |
Nr Exposed | 1 |
Gravity | 5 |
FTA Current Penalty | 0.0 |
Citation text line | 29 CFR 1926.404(f)(6): The path to ground from circuits, equipment, or enclosures was not permanent and continuous: a) Parking Garage near front of the building: On or about January 23, 2015 There was no ground on the temporary outlet which had been mounted on the concrete column which employees used to power portable tools. |
Inspection Type | Prog Related |
Scope | Complete |
Safety/Health | Safety |
Close Conference | 2012-03-22 |
Case Closed | 2012-10-04 |
Related Activity
Type | Inspection |
Activity Nr | 283118 |
Safety | Yes |
Type | Inspection |
Activity Nr | 283137 |
Safety | Yes |
Violation Items
Citation ID | 01001 |
Citaton Type | Serious |
Standard Cited | 19260405 A02 II E |
Issuance Date | 2012-09-17 |
Current Penalty | 2100.0 |
Initial Penalty | 3000.0 |
Final Order | 2012-09-28 |
Nr Exposed | 3 |
Gravity | 5 |
FTA Current Penalty | 0.0 |
Citation text line | 29 CFR 1926.405(a)(2)(ii)(E): Lamps used in temporary wiring for general illumination were not protected from accidental contact or breakage: Located at 227 Grand Street, Brooklyn, NY On or about 3/22/2012 a) a) Temporary lights for general illumination were not protected from accidental contact by employees by a cage or cover throughout the 2nd floor. |
Citation ID | 01002 |
Citaton Type | Serious |
Standard Cited | 19260405 A02 II F |
Issuance Date | 2012-09-17 |
Current Penalty | 1700.0 |
Initial Penalty | 2400.0 |
Final Order | 2012-09-28 |
Nr Exposed | 3 |
Related Event Code (REC) | Imminent Danger |
Gravity | 5 |
FTA Current Penalty | 0.0 |
Citation text line | 29 CFR 1926.405(a)(2)(ii)(F): Temporary lights were suspended by their electric cords when such lights and cords were not designed for suspension: Located at 227 Grand Street, Brooklyn, NY On or about 3/22/2012 a) Temporary lights for general illumination throughout the 2nd floor were suspended by their electric cords/wires and neither lights or cords/wires were designed for such suspension. |