Citation ID |
01001 |
Citaton Type |
Serious |
Standard Cited |
19100107 D02 |
Issuance Date |
2023-05-02 |
Abatement Due Date |
2023-06-05 |
Current Penalty |
1506.75 |
Initial Penalty |
2009.0 |
Final Order |
2023-06-09 |
Nr Instances |
1 |
Nr Exposed |
3 |
Related Event Code (REC) |
Complaint |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.107(d)(2): Spraying area(s) were not provided with mechanical ventilation adequate to remove flammable vapors, mists or powders to a safe location and to confine and control combustible residues: In the adhesive spray area. The spray application of adhesive containing methylene chloride, propane and methane (flammable gasses) did not incorporate a mechanical exhaust ventilation system to remove the accumulation of flammable vapors generated by the process. On or about November 9, 2022. Note: The employer is required to submit abatement certification for this item in accordance with 29 CFR 1903.19. |
|
Citation ID |
01002 |
Citaton Type |
Serious |
Standard Cited |
19100107 G02 |
Issuance Date |
2023-05-02 |
Current Penalty |
1506.75 |
Initial Penalty |
2009.0 |
Final Order |
2023-06-09 |
Nr Instances |
1 |
Nr Exposed |
2 |
Related Event Code (REC) |
Complaint |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.107(g)(2):All spraying areas were not kept as free from the accumulation of deposits of combustible residues as practical, with cleaning conducted daily if necessary: In the adhesive spray area. The spray application of adhesive containing methylene chloride, propane and methane (flammable gasses) created an accumulation of combustible deposits of the table top and walls. The accumulation was allowed to collect on the surfaces. On or about November 9, 2022. |
|
Citation ID |
01003A |
Citaton Type |
Serious |
Standard Cited |
19100134 C01 I |
Issuance Date |
2023-05-02 |
Abatement Due Date |
2023-06-05 |
Current Penalty |
1506.75 |
Initial Penalty |
2009.0 |
Final Order |
2023-06-09 |
Nr Instances |
1 |
Nr Exposed |
1 |
Related Event Code (REC) |
Complaint |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
1910.134(c)(1)(i): Where respirators were necessary to protect the health of the employee or whenever respirators were required by the employer, the employer did not establish and implement a written respiratory protection program with worksite-specific procedures. In the adhesive spray area. The employer did not have a written respiratory protection program for the adhesive spray applicator who was required to wear a tight fitting elastomeric respirator. On or about March 8, 2023 Note: The employer is required to submit abatement certification for this item in accordance with 29 CFR 1903.19. |
|
Citation ID |
01003B |
Citaton Type |
Serious |
Standard Cited |
19100134 E01 |
Issuance Date |
2023-05-02 |
Abatement Due Date |
2023-06-05 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2023-06-09 |
Nr Instances |
1 |
Nr Exposed |
1 |
Related Event Code (REC) |
Complaint |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
1910.134(e)(1): The employer did not provide a medical evaluation to determine the employee's ability to use a respirator, before the employee was fit tested or required to use the respirator in the workplace: In the spray adhesive application area, a medical evaluation for the spray adhesive applier required to wear a tight fitting elastomeric respirator was not conducted. On or about March 8, 2023 Note: The employer is required to submit abatement certification for this item in accordance with 29 CFR 1903.19. |
|
Citation ID |
01003C |
Citaton Type |
Serious |
Standard Cited |
19100134 F02 |
Issuance Date |
2023-05-02 |
Abatement Due Date |
2023-06-05 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2023-06-09 |
Nr Instances |
1 |
Nr Exposed |
1 |
Related Event Code (REC) |
Complaint |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
1910.134(f)(2): Employee(s) using tight-fitting facepiece respirators were not fit tested prior to initial use of the respirator: In the adhesive spray application area, The adhesive applicator was not fit tested for a tight fitting elastomeric respirator. On or about March 8, 2023 Note: The employer is required to submit abatement certification for this item in accordance with 29 CFR 1903.19. |
|
Citation ID |
01003D |
Citaton Type |
Serious |
Standard Cited |
19100134 K |
Issuance Date |
2023-05-02 |
Abatement Due Date |
2023-06-05 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2023-06-09 |
Nr Instances |
1 |
Nr Exposed |
1 |
Related Event Code (REC) |
Complaint |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.134(k):The employer did not provided effective training to employees who are required to use respirators: In the adhesive spray area. The company did not provide training for the adhesive spray applicator who was required to wear a tight fitting elastomeric respirator. On or about March 8, 2023 Note: The employer is required to submit abatement certification for this item in accordance with 29 CFR 1903.19. |
|
Citation ID |
01004 |
Citaton Type |
Serious |
Standard Cited |
19101052 L01 |
Issuance Date |
2023-05-02 |
Abatement Due Date |
2023-06-05 |
Current Penalty |
1506.75 |
Initial Penalty |
2009.0 |
Final Order |
2023-06-09 |
Nr Instances |
1 |
Nr Exposed |
3 |
Related Event Code (REC) |
Complaint |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.1052(l)(1):The employer did not provide information and training for each affected employee prior to or at the time of initial assignment to a job involving potential exposure to methylene chloride: In the adhesive spray area. The spray application of adhesive containing methylene chloride. . The employees were not notified of the potential exposure and associated hazards created by the spray application of the HELMISTIK 1685 adhesive containing methylene chloride. On or about November 9, 2022. Note: The employer is required to submit abatement certification for this item in accordance with 29 CFR 1903.19. |
|
Citation ID |
02001 |
Citaton Type |
Other |
Standard Cited |
19101200 G08 |
Issuance Date |
2023-05-02 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2023-06-09 |
Nr Instances |
1 |
Nr Exposed |
3 |
Related Event Code (REC) |
Complaint |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.1200(g)(8): The employer did not maintain in the workplace copies of the required safety data sheets for each hazardous chemical: At the workplace. The Material Safety Data Sheets in use were not updated to Safety Data Sheets. On or about November 9, 2022. |
|
Citation ID |
02002 |
Citaton Type |
Other |
Standard Cited |
19101052 D01 I A |
Issuance Date |
2023-05-02 |
Abatement Due Date |
2023-06-05 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2023-06-09 |
Nr Instances |
1 |
Nr Exposed |
1 |
Related Event Code (REC) |
Complaint |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.1052(d)(1)(i)(A):The employer did not determine each employee's exposure by taking a personal breathing zone air sample of each employee's exposure: In the adhesive spray area. The spray application of adhesive containing methylene chloride. The employer did not determine the spray adhesive applicator's level of exposure to methylene chloride. On or about March 8, 2023. Note: The employer is required to submit abatement certification for this item in accordance with 29 CFR 1903.19. |
|