346781073
|
0216000
|
2023-06-20
|
717 SOUTH 3RD AVE., MOUNT VERNON, NY, 10550
|
|
Inspection Type |
Fat/Cat
|
Scope |
NoInspection
|
Safety/Health |
Safety
|
Close Conference |
2023-06-20
|
Case Closed |
2023-11-06
|
Related Activity
Type |
Accident |
Activity Nr |
2044248 |
|
|
340182120
|
0216000
|
2014-11-06
|
717 SOUTH 3RD. AVE., MOUNT VERNON, NY, 10550
|
|
Inspection Type |
Referral
|
Scope |
Complete
|
Safety/Health |
Safety
|
Close Conference |
2014-11-06
|
Case Closed |
2015-03-23
|
Related Activity
Type |
Referral |
Activity Nr |
918387 |
Safety |
Yes |
|
Violation Items
Citation ID |
01001 |
Citaton Type |
Serious |
Standard Cited |
19100024 H |
Issuance Date |
2015-02-26 |
Current Penalty |
1260.0 |
Initial Penalty |
2100.0 |
Final Order |
2015-03-13 |
Nr Instances |
1 |
Nr Exposed |
2 |
Related Event Code (REC) |
Referral |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.24(h): Standard railings were not provided on the open sides of all exposed stairways and stair platforms: On or about 11/6/15 Location: Welding Area a) A five step concrete stairway in the welding room did not have standard railings on either side. |
|
Citation ID |
01002 |
Citaton Type |
Serious |
Standard Cited |
19100101 B |
Issuance Date |
2015-02-26 |
Current Penalty |
1260.0 |
Initial Penalty |
2100.0 |
Final Order |
2015-03-13 |
Nr Instances |
2 |
Nr Exposed |
2 |
Related Event Code (REC) |
Referral |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.101(b): "Compressed gases." The in-plant handling, storage, and utilization of all compressed gases in cylinders, portable tanks, rail tankcars, or motor vehicle cargo tanks was not in accordance with Compressed Gas Association Pamphlet P-1-1965, which is incorporated by reference as specified in Sec. 1910.6: Location: Welding Area On or about: 11/6/2014 a) The Argon cylinder in the welding area (station 1) was stored without being properly secured from falling over. b) The Argon cylinder in the welding area (station 2) was stored without being properly secured from falling over. |
|
Citation ID |
01003 |
Citaton Type |
Serious |
Standard Cited |
19100212 A01 |
Issuance Date |
2015-02-26 |
Current Penalty |
2100.0 |
Initial Penalty |
3500.0 |
Final Order |
2015-03-13 |
Nr Instances |
2 |
Nr Exposed |
2 |
Related Event Code (REC) |
Referral |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.212(a)(1): Types of guarding. One or more methods of machine guarding were not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks. Examples of guarding methods are-barrier guards, two-hand tripping devices,electronic safety devices, etc.: Location: Welding Area On or about: 11/6/14 a) Employees used a chop saw which was not guarded to prevent employees from coming into contact with the rotating blade. b) Employees used a chop saw which did not have a guard on the foot pedal to prevent employees from unintended operation by accidentally stepping onto the foot control. |
|
Citation ID |
01004 |
Citaton Type |
Serious |
Standard Cited |
19100215 A04 |
Issuance Date |
2015-02-26 |
Current Penalty |
1260.0 |
Initial Penalty |
2100.0 |
Final Order |
2015-03-13 |
Nr Instances |
1 |
Nr Exposed |
1 |
Related Event Code (REC) |
Referral |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.215(a)(4): Work rest(s) on grinding machinery were not adjusted closely to the wheel with a maximum opening of one eighth inch: Location: Welding area On or about:11/6/14 a) The Baldor abrasive wheel did not have a work rest. |
|
Citation ID |
01005 |
Citaton Type |
Serious |
Standard Cited |
19100215 B09 |
Issuance Date |
2015-02-26 |
Current Penalty |
1260.0 |
Initial Penalty |
2100.0 |
Final Order |
2015-03-13 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.215(b)(9): The distance between the abrasive wheel periphery(s) and the adjustable tongue or the end of the safety guard peripheral member at the top exceeded one fourth inch: Location: Welding area On or about: 11/6/14 a) The Baldon abrasive wheel was missing a tongue guard. |
|
Citation ID |
01006 |
Citaton Type |
Serious |
Standard Cited |
19100303 B01 |
Issuance Date |
2015-02-26 |
Current Penalty |
2100.0 |
Initial Penalty |
3500.0 |
Final Order |
2015-03-13 |
Nr Instances |
7 |
Nr Exposed |
2 |
Related Event Code (REC) |
Referral |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.303(b)(1): Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees: On or about 10/28/14 Location: Welding Area a) The conduit protection for the wires connected to the spot welding transformers were detached and separated exposing the wires to abrasion. |
|
Citation ID |
01007 |
Citaton Type |
Serious |
Standard Cited |
19100303 F |
Issuance Date |
2015-02-26 |
Current Penalty |
1260.0 |
Initial Penalty |
2100.0 |
Final Order |
2015-03-13 |
Nr Instances |
3 |
Nr Exposed |
2 |
Related Event Code (REC) |
Referral |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.303(f): Each service, feeder and branch circuit, at its disconnecting means or over current device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: On or about 11/6/14 Location: Welding Area a) The 110 volt circuit breaker panel in (station 1) did not have the individual breakers labled to indicate their purpose. b) The 110 volt circuit breaker panel in (station 2) did not have the individual breakers labled to indicate their purpose. c) The 110 volt circuit breaker panel (saw area) did not have the individual breakers labled to indicate their purpose. |
|
Citation ID |
01008 |
Citaton Type |
Serious |
Standard Cited |
19100303 G01 I |
Issuance Date |
2015-02-26 |
Current Penalty |
1260.0 |
Initial Penalty |
2100.0 |
Final Order |
2015-03-13 |
Nr Instances |
2 |
Nr Exposed |
2 |
Related Event Code (REC) |
Referral |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.303(g)(1)(i): The dimension of the working space in the direction of access to live parts operating at 600 volts or less and likely to require examination, adjustment, servicing, or maintenance while alive was less than indicated in Table S1: On or about 11/6/14 Location: Welding Area a) The clearance in front of the circuit breaker panel in work station 1 was less than 30 inches. The area directly in front of the panel was blocked. b) The clearance in front of the circuit breaker panel in work station 2 was less than 30 inches. The area directly in front of the panel was blocked. |
|
Citation ID |
01009 |
Citaton Type |
Serious |
Standard Cited |
19100305 B01 II |
Issuance Date |
2015-02-26 |
Current Penalty |
2100.0 |
Initial Penalty |
3500.0 |
Final Order |
2015-03-13 |
Nr Instances |
1 |
Nr Exposed |
2 |
Related Event Code (REC) |
Referral |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: On or about: 11/6/14 Location: Welding Area a) Numerous breaker openings in the 110 volt circuit breaker panel in the electrical closet were open exposing live electrical buses and wiring. |
|
|
340047976
|
0216000
|
2014-10-29
|
717 SOUTH 3RD AVE., MOUNT VERNON, NY, 10550
|
|
Inspection Type |
Complaint
|
Scope |
Partial
|
Safety/Health |
Health
|
Close Conference |
2014-10-29
|
Case Closed |
2014-12-16
|
Related Activity
Type |
Complaint |
Activity Nr |
917887 |
Health |
Yes |
|
Violation Items
Citation ID |
01001 |
Citaton Type |
Serious |
Standard Cited |
19100101 B |
Issuance Date |
2014-12-05 |
Current Penalty |
2100.0 |
Initial Penalty |
2800.0 |
Final Order |
2014-12-31 |
Nr Instances |
2 |
Nr Exposed |
10 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.101(b): The in-plant handling, storage, and utilization of all compressed gases in cylinders, portable tanks, rail tankcars, or motor vehicle cargo tanks were not in accordance with Compressed Gas Association Pamphlet P-1-1965, which is incorporated by reference as specified in CFR 1910.6: Location; Welding station Compressed gas cylinders of argon were not secured from falling; on or about 10/29/14. |
|
Citation ID |
01002 |
Citaton Type |
Serious |
Standard Cited |
19100107 L04 I |
Issuance Date |
2014-12-05 |
Current Penalty |
2100.0 |
Initial Penalty |
2800.0 |
Final Order |
2014-12-31 |
Nr Instances |
1 |
Nr Exposed |
2 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.107(l)(4)(i): All areas were not kept free of the accumulation of powder coating dust: Location: Powder Spraying room a) The Spectrum 11 Powder System was covered with fine powder on working and walking surfaces; on or a about 10/29/14. |
|
Citation ID |
01003 |
Citaton Type |
Serious |
Standard Cited |
19100252 B02 III |
Issuance Date |
2014-12-05 |
Current Penalty |
2100.0 |
Initial Penalty |
2800.0 |
Final Order |
2014-12-31 |
Nr Instances |
5 |
Nr Exposed |
10 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.252(b)(2)(iii): Workers and other persons adjacent to the welding area were not protected from the rays by noncombustible or flameproof screens or shields: Location: Welding stations a) Welding stations were not completely enclosed with welding curtains; on or about 10/29/14. |
|
Citation ID |
02001 |
Citaton Type |
Other |
Standard Cited |
19100141 D01 |
Issuance Date |
2014-12-05 |
Abatement Due Date |
2014-12-17 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2014-12-31 |
Nr Instances |
2 |
Nr Exposed |
60 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.141(d)(1): Washing facilities were not maintained in a sanitary condition: Location: Production area Bathrooms used by employees were not maintained in a sanitary condition; on or about 10/29/14 |
|
Citation ID |
02002 |
Citaton Type |
Other |
Standard Cited |
19100157 C01 |
Issuance Date |
2014-12-05 |
Abatement Due Date |
2014-12-17 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2014-12-31 |
Nr Instances |
3 |
Nr Exposed |
60 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries: Location: Production Area a) Fire extinguishers were not readily accessible as they were blocked by cardboard boxes, a chair, and a table; on or about 10/29/14. |
|
|
313516569
|
0215000
|
2009-07-07
|
409 NEWPORT ST, BROOKLYN, NY, 11207
|
|
Inspection Type |
Planned
|
Scope |
NoInspection
|
Safety/Health |
Health
|
Close Conference |
2009-07-07
|
Emphasis |
L: HHHT50
|
Case Closed |
2009-07-07
|
|