Citation ID |
01001A |
Citaton Type |
Serious |
Standard Cited |
19100024 H |
Issuance Date |
2014-11-03 |
Abatement Due Date |
2014-12-06 |
Current Penalty |
816.0 |
Initial Penalty |
1360.0 |
Final Order |
2014-11-24 |
Nr Instances |
3 |
Nr Exposed |
3 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.24(h): Standard railings were not provided on the open sides of all exposed stairways and stair platforms: a) Dryer Room, on or about 10/15/14: A fixed stairway and platform with six risers was not provided with standard railings. b) Manufacturing Area, on or about 10/15/14: A stairway and platform with five risers for access to the hopper for Cincinnati Milacron press #19 was not provided with midrails on the stairway. c) Manufacturing Area, on or about 10/15/14: A stairway and platform with seven risers for access to the hopper for Cincinnati Milacron press #18 was not provided with midrails on the stairway and platform. Abatement certification must be submitted for these items. |
|
Citation ID |
01001B |
Citaton Type |
Serious |
Standard Cited |
19100024 F |
Issuance Date |
2014-11-03 |
Abatement Due Date |
2014-12-06 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2014-11-24 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.24(f): Rise height and tread width were not uniform throughout any flight of stairs including any foundation structure used as one or more treads of the stairs: a) Dryer Room, on or about 10/15/14: A fixed stairway with six risers to the dryer unit was not uniform throughout. Stair rise measured from 6 1/4 inches to 13 3/4 inches. Abatement certification must be submitted for this item. |
|
Citation ID |
01001C |
Citaton Type |
Serious |
Standard Cited |
19100024 D |
Issuance Date |
2014-11-03 |
Abatement Due Date |
2014-12-06 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2014-11-24 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.24(d): Fixed stairways did not have a minimum width of 22 inches; a) Dryer Room, on or about 10/15/14: A fixed stairway to the dryer platform measured only 21 inches wide. Abatement certification must be submitted for this item. |
|
Citation ID |
01002A |
Citaton Type |
Serious |
Standard Cited |
19100036 D01 |
Issuance Date |
2014-11-03 |
Abatement Due Date |
2014-12-06 |
Current Penalty |
1224.0 |
Initial Penalty |
2040.0 |
Final Order |
2014-11-24 |
Nr Instances |
3 |
Nr Exposed |
10 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.36(d)(1): Exit door was locked. Employees must be able to open an exit route door from the inside at all times without keys, tools, or special knowledge: a) Front Manufacturing Area, on or about 10/15/14: Exit door was locked. b) Storage, Back Corner, on or about 10/15/14: Exit door was locked. c) Mold Storage Area, on or about 10/15/14: Exit door was locked. Abatement certification must be submitted for these items. - |
|
Citation ID |
01002B |
Citaton Type |
Serious |
Standard Cited |
19100037 A04 |
Issuance Date |
2014-11-03 |
Abatement Due Date |
2014-11-21 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2014-11-24 |
Nr Instances |
2 |
Nr Exposed |
10 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.37(a)(4): Safeguard(s) designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting), were not in proper working order at all times: a) Front Manufacturing Area, on or about 10/15/14: Emergency lighting at the front exit door was not functioning. b) Main employee entrance, on or about 10/15/14: Emergency lighting at the exit door was not functioning. Abatement certification must be submitted for these items. |
|
Citation ID |
01003 |
Citaton Type |
Serious |
Standard Cited |
19100242 B |
Issuance Date |
2014-11-03 |
Abatement Due Date |
2014-11-21 |
Current Penalty |
612.0 |
Initial Penalty |
1020.0 |
Final Order |
2014-11-24 |
Nr Instances |
2 |
Nr Exposed |
1 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.242(b): Compressed air used for cleaning purposes was not reduced to less than 30 p.s.i.: a) Back Machine Shop, on or about 10/15/14: Compressed air guns at the Manhattan drill press and at the Bridgeport milling machine measured >100 psi. Abatement certification must be submitted for this item. |
|
Citation ID |
01004A |
Citaton Type |
Serious |
Standard Cited |
19100305 B01 II |
Issuance Date |
2014-11-03 |
Abatement Due Date |
2014-11-13 |
Current Penalty |
1020.0 |
Initial Penalty |
1700.0 |
Final Order |
2014-11-24 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: a) Front Manufacturing Area, on or about 10/15/14: A circuit breaker panel behind the Niigata press #14A had three blanks missing. Abatement certification must be submitted for this item. |
|
Citation ID |
01004B |
Citaton Type |
Serious |
Standard Cited |
19100305 G02 III |
Issuance Date |
2014-11-03 |
Abatement Due Date |
2014-11-21 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2014-11-24 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws: a) Front Manufacturing Area, on or about 10/15/14: Flexible cord providing current to a fluorescent light fixture for the workbench at the Cincinnati Milacron press #3 was pulled loose at the plug fitting. Abatement certification must be submitted for this item. |
|
Citation ID |
02001 |
Citaton Type |
Other |
Standard Cited |
19100178 P01 |
Issuance Date |
2014-11-03 |
Abatement Due Date |
2014-11-21 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2014-11-24 |
Nr Instances |
1 |
Nr Exposed |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.178(p)(1): Powered industrial truck(s) found to be in need of repair, defective, or in any way unsafe had not been taken out of service until restored to safe operating condition(s) a) Storage Area, on or about 10/15/14: The propane cylinder on a Hyster #10 forklift was not lined up with the locater pin. Abatement certification must be submitted for this item. |
|
Citation ID |
02002 |
Citaton Type |
Other |
Standard Cited |
19100303 B02 |
Issuance Date |
2014-11-03 |
Abatement Due Date |
2014-12-06 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2014-11-24 |
Nr Instances |
4 |
Nr Exposed |
4 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) Front Manufacturing Area, on or about 10/15/14: A strip outlet on a workbench powering a buffer was not being used in accordance with the listing and labeling. b) Front Manufacturing Area, on or about 10/15/14: A strip outlet on a workbench at the Cincinnati Milacron press #3 was not being used in accordance with the listing and labeling. c) Front Manufacturing Area, on or about 10/15/14: A strip outlet on a workbench at the Cincinnati Milacron press #22 was not being used in accordance with the listing and labeling. d) Front Manufacturing Area, on or about 10/15/14: A strip outlet on a workbench at the Cincinnati Milacron press #21 was not being used in accordance with the listing and labeling. Abatement certification must be submitted for these items. |
|